Rockwell Automation Publication 750-TG101A-EN-P - June 2022
165
Chapter 6 Frame 7 Renewal Kits Installation
12. If the DC bus bars are installed, complete steps a…d to remove the
stirring fan assembly.
a. Loosen the two lower M5 Torx screws that secure the lower stirring fan
assembly to the chassis.
b. Remove the upper M6 x 16 mm Torx screw that secures the upper fan
assembly to the chassis side bracket.
c. Slide the fan assembly to the right, lift the fan assembly off the screws,
and remove the assembly.
d. Disconnect the fan-assembly power wire harness connectors P5 and
P6 from connectors J5 and J6, respectively, on the power interface
circuit board (left side of the fan assembly).
12b
M6 x 16 mm
T30
5.2 N
•
m (46.0 lb
•
in)
12a
M5 (2x)
T30
4.9 N
•
m (43.0 lb
•
in)
P5 and P6
12c
12d