4
Rockwell Automation Publication 1756-IN048D-EN-P - March 2021
GuardLogix 5580 Controllers Installation Instructions
Parts List
The controller ships with these parts:
•
A key for the mode switch
•
2 GB Secure Digital Card (1784-SD2), pre-installed in the controller
IEC Hazardous Location Approval
The following applies to products with IECEx certification:
• Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and
for short periods. Such locations correspond to Zone 2 classification to IEC 60079-0.
• The type of protection is Ex nA IIC T4 Gc according to IEC 60079-15.
• Such modules comply to Standards IEC 60079-0:2011, IEC 60079-15:2010, reference IECEx certificate number IECExUL14.0008X.
• May have catalog numbers followed by a "K" to indicate a conformal coating option.
Special Conditions for Safe Use
WARNING:
• This equipment is not resistant to sunlight or other sources of UV radiation.
• This equipment shall be mounted in an ATEX/IECEx Zone 2 certified enclosure with a minimum ingress protection rating of at least IP54
(as defined in EN/IEC 60079-15) and used in an environment of not more than Pollution Degree 2 (as defined in EN/IEC 60664-1) when
applied in Zone 2 environments. The enclosure must be accessible only by the use of a tool.
• This equipment shall be used within its specified ratings defined by Rockwell Automation.
• Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 140% of the rated
voltage when applied in Zone 2 environments.
• The instructions in the user manual shall be observed.
• This equipment must be used only with ATEX/IECEx certified Rockwell Automation backplanes.
• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
• The USB port is intended for temporary local programming purposes only and not intended for permanent connection. Do not use the
USB port in hazardous locations.
Environment and Enclosure
ATTENTION:
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as
defined in EN 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication
services in such environments.
This equipment is supplied as open-type equipment for indoor use. It must be mounted within an enclosure that is suitably designed for
those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from
accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame,
complying with a flame spread rating of 5VA or be approved for the application if non-metallic. The interior of the enclosure must be
accessible only by the use of a tool. Subsequent sections of this publication may contain more information regarding specific enclosure
type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following:
• Industrial Automation Wiring and Grounding Guidelines, publication
, for more installation requirements
• NEMA Standard 250 and EN/IEC 60529, as applicable, for explanations of the degrees of protection provided by different types of
enclosure.
Programmable Electronic Systems (PES)
ATTENTION:
Personnel responsible for the application of safety-related Programmable Electronic Systems (PES) shall be aware of the safety
requirements in the application of the system and shall be trained in using the system.
IMPORTANT
Any illustrations, charts, sample programs, and layout examples shown in this publication are intended solely for the purposes of example. Since
there are many variables and requirements associated with any particular installation, Rockwell Automation does not assume responsibility or
liability for actual use based upon the examples shown in this publication.