GuardLogix® Controllers Logic Integration
Chapter 3
5. Type the
ZoneName
from your Safety Zone Configuration worksheet into the two map tags on the Import
Configuration dialog.
6. For the
ModuleName1
through
ModuleName6
Add-On Instruction tags, click
ModuleName
and then click the pull-
down arrow to browse to your configured GuardIO_AOI tags as listed in your Safety Zone configuration worksheet.
7. Double-click the GuardIO_AOI tag to select it.
If your zone has less than 6 safety modules, leave any unused tags names as is.
If your zone has more than 6 safety modules, you will need to add more instructions after the import is complete.
This examples shows two Guard I/O modules configured with
ModuleNames
‘CellGuard1’ and ‘CellGuard2’
8. Click OK to complete the import.