172
Rockwell Automation Publication IASIMP-QS005H-EN-P - April 2016
Chapter 6
Safety System Application Guide
Code (hex)
Error Content
Probable Cause
Recommended Action
00
Reserved
01
No error
02
Signal over-range
Signal Exceeded Configured Range
Check Field Wiring/Power
03
Signal under-range
Signal Below Configured Range
Check Field Wiring/Power
04
Signal test failure
Undefined Error for IE4S
If Problem Persists, Replace Module
05
Dual-channel discrepancy
Exceeded Tolerance Between Dual Channels
Check Field Sensors to for Discrepancy
06
Error in the other dual-channel input
Partner Channel Faulted
Troubleshoot Partner Channel Fault
08
Reserved
100
Sensor supply overcurrent
Exceeded Specification
Check Field Wiring/Sensor Power Draw
101
Sensor supply undercurrent
Too Little Current Drawn from Sensor Power
Check Field Wiring/Sensor Power Draw
102
ADC or CPU Timing Fault
ADC Missed a Clock, Failed a Sync or Watchdog
If Problem Persists, Replace Module
103
3.3V undervoltage
3.3V Supply Voltage was Detected Too Low
If Problem Persists, Replace Module
104
3.3V overvoltage
3.3V Supply Voltage was Detected Too High
If Problem Persists, Replace Module
105
CPU fault
ADC Failed Register, Instruction, or Flag Diag
If Problem Persists, Replace Module
106
Flash fault
FLASH Test Detected Bit Errors
If Problem Persists, Replace Module
107
RAM fault
RAM Test Detected Bit Errors
If Problem Persists, Replace Module
108
Single-channel discrepancy
Dual Measurements of Single Channel Disagree
If Problem Persists, Replace Module
109
Tach Dual Low
Both Channels LOW at the Same Time
Check Sensor Signal Timing
110
Undefined error
If Problem Persists, Replace Module
111
Flash enable fault
ADC's FLASH Memory Drawing Too Much Current
If Problem Persists, Replace Module
112
Serial pattern fault
Serial Communication Pattern Errors Detected
Check Field Wiring for Proper Grounding/Shielding.
Verify that Temperature Within Enclosure is not
Excessive. If Problem Persists, Replace Module
113
Channel uniqueness fault
Pulse Testing Revealed Improper Channel
If Problem Persists, Replace Module
114
Watchdog fault
ADC Watchdog Timed Out
If Problem Persists, Replace Module
115
Sync timeout fault
ADC Conversion Out of Sync
If Problem Persists, Replace Module
116
Missing clock fault
ADC Detected a Missing Clock
If Problem Persists, Replace Module
117
SCI Tx fault
Serial Communication Bit Errors Detected
Check Field Wiring for Proper Grounding/Shielding.
Verify that Temperature Within Enclosure is not
Excessive.
118
ADC fault
ADC Test Pattern Failure
If Problem Persists, Replace Module
119
ADC neighbor 1.8V fault
ADC Detected Out-of-Range Voltage on its Partner
If Problem Persists, Replace Module
120
ADC channel configuration mismatch
Dual ADCs are Not Configured the Same
If Problem Persists, Replace Module
121
SPI sequence number mismatch
Serial Comm State Machines are Out of Sync
If Problem Persists, Replace Module
122
Runtime 3.3V over-under-voltage error
3.3V Supply Voltage was Too High or Too Low
If Problem Persists, Replace Module
123
Reserved
124
Reserved
125
Field I/O power is missing
24V Power is not Within Specification
Check Field Power Supply and Wiring
126
Startup 3.3V over-under-voltage error
OV-UV Detector Failed Startup Test
If Problem Persists, Replace Module
127
Sensor power/input wiring error
Sensor Power to Input Signal Violation Detected
Check Field Wiring