POINT I/O Protected Sink Output Module
21
Publication
1734-IN585C-EN-E - December 2005
Troubleshoot the Module
Indication
Probable Cause
Recommended Action
Module Status
Off
No power applied to device.
Apply power applied to device.
Solid Green
Device is operating normally.
Device is operating normally.
Flashing Green
Device needs commissioning
due to configuration missing,
incomplete, or incorrect.
Configure device properly.
Flashing Red
Recoverable fault is present.
1. Cycle power.
2. Configure device properly if
needed.
3. If condition persists, replace
device.
Solid Red
Unrecoverable fault may
require device replacement.
Replace device.
Flashing Red/Green
Device is in self-test.
None
Module Status
Network Status
Status of Output 0
Status of Output 1
Status of Output 2
1734-OV2E
1734-OV4E
1734-OV8E
Status of Output 0 & 4
Status of Output 1 & 5
Status of Output 2 & 6
Status of Output 3 & 7
Status of Output 3
24VDC
Sink
Output
Module
Status
Network
Status
1734
OV8E
NODE:
0
1
2
3
4
5
6
7
24VDC
Sink
Output
Module
Status
Network
Status
1734
OV4E
NODE:
0
1
2
3
2
24VDC
Sink
Output
Module
Status
Network
Status
1734
OV2E
NODE:
0
1