1606-XLE240EP 24V, 10A; Single Phase Input
10000126343
(Version 00)
www.ab.com
Page 13
22.
P
HYSICAL
D
IMENSIONS AND
W
EIGHT
Weight
800g
/
1.76lb
DIN-Rail
Use 35mm DIN-rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm.
The DIN-rail height must be added to the depth (117mm) to calculate the total required installation depth.
Fig. 22-1 Front view
Fig. 22-2 Side view
23.
I
NSTALLATION AND
O
PERATION
I
NSTRUCTIONS
Hazardous voltage inside device. Risk of electric shock, severe burns, or death.
•
Do not use the unit without proper earth connection (Protective Earth). Use the pin on the terminal block for earth connection and not one of
the screws on the housing.
•
Turn power off before working on the power supply. Protect against inadvertent re-powering.
•
Make sure the wiring is correct by following all local and national codes.
•
Do not open, modify or repair the unit.
•
Use caution to prevent any foreign objects from entering into the housing.
•
Do not use in wet locations or in areas where moisture or condensation can be expected.
Mounting Orientation:
Output terminal must be located on top and input terminal on the bottom. For other orientations see section 25.12.
Cooling:
Convection cooled, no forced cooling required. Do not cover ventilation grid (e.g. cable conduits) by more than 30%!
Installation clearances:
40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent
device is a heat source, 15mm clearance is recommended.
Service parts:
The unit does not contain any serviceable parts. The tripping of an internal fuse is caused by an internal defect.