Rockwell
Automation
1606-XLE240EP 24V, 10A; Single Phase Input
10000126343
(Version 00)
www.ab.com
Page 3
5.
AC-I
NPUT
AC
input
nom.
AC 100-120V / 200-
240V
auto-select input, see
AC input range
90-132Vac
100-120V range, continuous operation
180-264Vac
200-240V range, continuous operation
85-90Vac
Short term or with output derating
264-300Vac <
0.5s
Input
frequency
nom.
50 – 60Hz
±6%
AC 100V
AC 120V
AC 230V
Input
current
typ.
4.34A
3.73A
2.0A
at 24V, 10A see
Power factor *
typ.
0.61
0.59
0.57
at 24V, 10A see
Crest factor **
typ.
2.61
2.83
3.1
at 24V, 10A
Start-up
delay
typ. 700ms 800ms 850ms
Rise
time
typ.
35ms 35ms 35ms
0mF,
typ.
75ms
75ms
75ms
10mF, 24V, 10A, see
Turn-on
overshoot
max.
100mV 100mV 100mV
Turn-on
voltage
typ.
82Vac
82Vac
N / A
steady-state value, see
Shut-down
voltage
typ.
75Vac
75Vac
N / A
steady-state value, see
*
The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**
The crest factor is the mathematical ratio of the peak value to the RMS value of the input current waveform
Fig. 5-1 Input voltage range
Fig. 5-2 Turn-on behavior, definitions
Tu
rn
-o
n
90V
Rated input ranges
V
IN
P
OUT
264Vac
180V
Sh
u
t-
dow
n
132V
no
harm
from
132 to
180V
Range
100-
120V
Range
200-
240V
Start-up
delay
Rise
Time
O
ve
rs
hoot
- 5%
Output
Voltage
Intput
Voltage
Fig. 5-3 Input current vs. output load
Fig. 5-4 Power Factor vs. output load
12A
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6A
Input
Current, typ.
10 11
Output Current
230Vac
120
Vac
100
Vac
12A
2
3
4
6
8
0.35
0.4
10
Output Current
5
7
9
11
0.45
0.5
0.55
0.6
0.65
Power Factor, typ.
100Vac
120Vac
230Vac