Transport and positioning
Installation, use and maintenance manual – Next-R
21
2
2.4
MINIMUM CLEARANCE DISTANCES
2.4.1
Distances from combustible or
fl
ammable
materials
▶
Keep the appliance away from combustible or
fl
ammable
materials or components, in compliance with applicable
regulations.
2.4.2
Clearances around the appliance
The minimum clearance distances are required for safety,
operation and maintenance.
Axial gas unit heaters
Figure
2.2
Clearances
A
Gas unit heater width
B
Object or structure underneath the gas unit heater
B
> 350
mm
> 400 mm
< 3,5 m
> 2,2 m
> 200
mm
A
A
> 500 mm
The recommended height from the
fl
oor to the gas unit
heater base is 2,2 to 3,5 m (see Figure 2.2
21). In-
stalling the gas unit heaters at heights below 2,2 m from
the
fl
oor is not recommended.
Centrifugal gas unit heaters
The position of gas unit heaters with centrifugal fan must con-
sider the position of the hot air duct. This must be suitably sized
and veri
fi
ed in relation to the air
fl
ow rate and the head of the
centrifugal fan (Paragraph 3.4
The recommended height from the
fl
oor to the gas unit
heater base is 2,5 to 3,5 m (see Figure 2.2
21). We do
not recommend installing the gas unit heaters at heights
below 2,5 m from the
fl
oor.
Vertical down
fl
ow gas unit heaters
A minimum distance of 1 m from all sides is required around the
vertical down
fl
ow gas unit heater.
Table 2.1
22 shows recommended minimum and maximum
heights for installation and the air jet range to the
fl
oor, depend-
ing on the actual height of the gas unit heater from the
fl
oor
(indicated with H).
For vertical down
fl
ow gas unit heaters, the louvres of the
delivery grille must be in the fully open position.
Figure
2.3
Clearances
A
Air jet range
H
Gas unit heater installation height
> 1 m
H
> 1 m
> 1 m
A