![Robur Direct Digital Controller Скачать руководство пользователя страница 76](http://html.mh-extra.com/html/robur/direct-digital-controller/direct-digital-controller_installation-use-and-programming-manual_1471517076.webp)
Direct Digital Controller
74
Direct Digital Controller fw 4.013 – Ed. 01/2013
4.4.1.7 Multi DDC configuration
This represents the
fourth stage
of the configuration of Multi DDC plants (for further information consult
Paragraph 4.5.2.2– “Multi DDC
Binding”) and must be carried out with all the DDCs of the plant receiving
electrical current. The DDCs exchange information about the machine assigned to them, to determine whether
they must be co-ordinated in order to manage any units. This occurs when units, or modules of units, have
been assigned to more than one DDC, linked to the same plant.
All DDCs begin to display information about themselves and about the other DDCs present, as shown in
Figure 18. The first row shows information regarding the DDC on which data is being viewed. The following
rows regard the other DDCs present in the network. The figure below shows the parameters displayed during
configuration of Multi DDC plants.
Figure
18
–
EXAMPLE OF MACHINE CONFIGURATION MENU SCREEN
For all the DDCs in the plant, carry out the following operations:
1 - Select from the initial screen to gain access to the main menu.
2 - Select
to gain access to the System installation.
3 - Enter the installer password, if requested, on the numerical keypad that appears on the display.
4 - From the drop-down menu select
“DDC”
.
5 - Select
“Multi DDC Binding”
from the drop-down menu.
6 - Select
“Yes”
from the screen that appears.
7 - A screen appears on which the data described in
Figure 18
appears, regarding the DDC on which Multi
DDC configuration is being carried out.
8 - Repeat steps 1 to 7 on all other DDCs in the plant.
KEY:
A
DDC identification number (network ID).
B
Identification number of the chilled water production plant;
C
DDC function for the plant indicated at point B: M = Master; S =
Slave.
D
Identification number of the hot water production plant;
E
DDC function for the plant indicated at point D: M = Master; S =
Slave.
F
Scroll arrows for viewing the DDCs.
G
Exit
screen
H
Text describing the function of the icon selected.
I
The first row shows the data for the DDC on which Multi DDC
configuration is being carried out.
F
D
A
I
H
C
B
E
G