Direct Digital Controller
132
Direct Digital Controller fw 4.013 – Ed. 01/2013
Diagram only for 2 line plants with only one
consent available
Figure 26
– EXAMPLE OF EXTERNAL CONTROL PLANT CONNECTIONS FOR RYWm MODE
4.5.3.1.3 Instructions for operation in aRYW mode
In RYWa operating mode (
two-line hot/cold plants
only), selection of COOLING or HEATING operation is
managed by the external contacts RY and RW.
Closing the contacts R - Y of connector D located on the rear of the Direct Digital Controller (see Figure 13 on
page 54) entails:
Switching on the plant;
Passing to COOLING mode, if currently in heating mode;
Activation of the units.
Closing the contacts R - W of connector D located on the rear of the Direct Digital Controller (see Figure 13 on
page 54) entails:
Switching on the plant;
Passing to HEATING, mode, if currently in cooling mode;
Activation of the units.
Opening the R - Y or R - W contacts entails:
KEY:
R1
On/off command relay contacts (not supplied as standard)
RC1
Relay contacts for cooling system (not supplied as standard)
RC2
Relay contacts for heating system (not supplied as standard)
terminal 1 R
(24
Vac)
terminal 2 W
(heating
plant
consent)
terminal 3 Y
(cooling plant consent)
terminal 4 0
(0
Vac)
terminal 5 NA
Leave not connected
terminal 6 R
(24
Vac)
Diagram for 4 line plants and 2 line plants
with separate consents