26
The dimensions and weight of the appliance are given in Paragraph 2.4 TECHNICAL
DATA
→
11.
Supporting base
Always position the appliance on a flat level surface that is made of fireproof material
and able to sustain the weight of the appliance itself.
•
Installation at ground level
If a horizontal base is not available (see also "Supports and levelling"), it is necessary to
create a flat level base in concrete at least 100-150 mm larger than the dimensions of
the base of the appliance on each side.
For the dimensions refer to the tables in Paragraph 2.4 TECHNICAL DATA
→
11.
•
Installation on a terrace or roof
Position the appliance on a levelled flat surface made of fireproof material (see also
"Supports and levelling").
The structure of the building must be able to sustain the weight of the appliance ad-
ded to that of the supporting base.
For the weight refer to the tables in Paragraph 2.4 TECHNICAL DATA
→
11.
In addition, it is advisable to use flexible connections (anti-vibration joints) between
the appliance and the hydraulic and gas supply pipes.
Avoid positioning the appliance directly above rest areas or other areas that require
quiet.
Supports and levelling
The appliance must be correctly levelled by placing a level on the upper part of the
appliance.
If necessary, level the appliance with metal spacers, placing them appropriately in rela-
tion to the mounts; do not use wooden spacers as these degrade quickly.
Clearances
Position the appliance so as to maintain minimum clearances from combustible sur-
faces, walls or other appliances, as illustrated in Figure 4.1 Clearances
→
27.
Minimum clearances are necessary in order to be able to carry out maintenance ope-
rations and to be able to guarantee the correct flow of air required for combustion:
install a walkway around the appliance if necessary.
Position the appliance preferably out of range of rooms and/or environments where
strict silence is required, such as bedrooms, meeting rooms, etc.