Installation, Start-Up, Adjustment and Maintenance Manual
23
ACF60-00 HR – COOLING CAPACITY CORRECTION FACTORS [Btu/hr]
Table 10
– ACF60-00 HR - Cooling capacity multiplication correctional factors in air conditioning mode (no recovery) for
external air temperatures and water flow rates different from the nominal values reported in the table.
ACF60-00 HR – COOLING CAPACITY CORRECTION FACTORS [Btu/hr]
Table 11
– ACF60-00 HR - Cooling capacity multiplication correctional factors in air condirecovery mode for
external air temperatures and water flow rates different from the nominal values reported in the table.
OPERATIONAL MODE: AIR CONDITIONING ONLY
WATER DELIVERY TEMPERATURE °F
EXTERNAL AIR
TEMPERATURE
°F
37.4 41 44.6
48.2
32
0.98 0.99 1.01
1.03
41
0.98 0.99 1.01
1.03
50
0.98 0.99 1.01
1.03
59
0.98 0.99 1.01
1.03
68
0.98 0.99 1.01
1.03
77
0.97 0.99 1.01
1.03
86
0.90 0.98 1.01
1.03
95
0.67 0.87
1.00
1.02
104
— —
0.88
0.93
113
— —
0.67
0.78
OPERATIONAL MODE: AIR CONDIT RECOVERY
WATER DELIVERY TEMPERATURE °F
EXTERNAL AIR
TEMPERATURE
°F
37.4 41 44.6
48.2
32
0.97 0.98 1.00
1.02
41
0.97 0.98 1.00
1.02
50
0.97 0.98 1.00
1.02
59
0.97 0.98 1.00
1.02
68
0.97 0.98 1.00
1.02
77
0.96 0.98 1.00
1.02
86
0.89 0.97 1.00
1.02
95
0.73 0.91
1.00
1.02
104
— 0.89
0.95
0.96
113
— —
0.80
0.85