Installation, Start-Up, Adjustment and Maintenance Manual
10
HT VERSION
PERFORMANCE RATINGS
1
UNITS
ACF60-00 HT
Cooling Capacity
2
Nominal
Btu/hr
58,400
Gas Input (HHV)
Nominal
Btu/hr
94,900
°
F
131
Ambient Operating Temperature
Maximum
Minimum
°
F
32
Condenser Air Flow
3
Nominal
Minimum
CFM
CFM
6,000
2,000
Inlet (to the unit) Chilled Water
Temperature
Maximum
°
F
113
Outlet (to plant) Chilled Water
Temperature
Minimum
°
F
41
Chilled Water Flow
Nominal
Maximum
Minimum
GPM
11.8
14.1
11.0
Internal Pressure Drop
Feet of Head
psi
g
9.1
3.9
ELECTRICAL RATINGS
Required Voltage, 60 Hz, Single
Phase
4
V
208 - 230
Condenser Fan Motor HP
(Variable Speed)
Full Load / Locked Rotor
Nominal
-
A
1/2
3.1 / 6.2
Hydraulic Pump Motor HP
Full Load / Locked Rotor
Nominal
-
A
1/2
3.1 / 24.2
Premix Blower Motor HP
Full Load / Locked Rotor
Nominal
-
A
1/50
.55 / .75
Total Electrical Operating
Consumption
5
(Unit only)
kW .75
Minimum Circuit Ampacity
(MCA) (Unit only)
A
8.0
Maximum Over Current
Protection (MOCP)
Qty (2) - Field Supplied
A 10.9
PHYSICAL DATA
Refrigerant Type
-
R717
Unit Chilled Water Volume
6
Gallons
0.79
Chilled Water Entering and
Leaving Connections
7
FPT
1”
1/4
Gas Inlet Connection
FPT
1/2
Electrical Entrance Knockouts,
Diameter
Inches
7/8
Shipping Weight
Pounds
860
Operating Weight
Pounds
816
Width 33
1
/
2
Length 48
1
/
2
Dimensions
Height
Inches
50
3
/
4
Table 3
– ACF60-00 HT TECHNICAL DATA