To initialize the data stream, 0x0200 must be written with the function 16 (0x10) in register 410 (019A).
Request is: 09 10 01 9A 00 01 02 02 00 CD CA
Hex format: 0x09 0x10 0x01 0x9A 0x00 0x01 0x02 0x02 0x00 0xCD 0xCA
Bits
Description
09
SlaveID
10
Function Code 16 (Preset Multiple Registers)
019A
Address of the first register
0001
Number of registers requested (1)
02
Number of data bytes to follow (1 registers x 2 bytes/ register = 2 bytes)
0200
Value written to register 0x019A
CDCA
Cycle Redundancy Check (CRC)