SECTION 11: O
PERATION
AND
M
AINTENANCE
61
all heater condition should be thoroughly inspected.
NOTE:
Gas flow and burner ignition are among the
first things that should be inspected.
Please
for suggested
items to inspect.
11.5 Maintenance Checklist
Installation Code and Annual Inspections:
All installation and service of NDUSTRIA
™
equipment must be performed by a contractor
qualified in the installation and service of equipment
sold and supplied by NDUSTRIA and conform to all
requirements set forth in the NDUSTRIA
™
manuals
and all applicable governmental authorities
pertaining to the installation, service, operation and
labeling of the equipment.
To help facilitate optimum performance and safety,
NDUSTRIA recommends that a qualified contractor
conduct, at a minimum, annual inspections of your
NDUSTRIA
™
equipment and perform service where
necessary, using only replacement parts sold and
supplied by NDUSTRIA.
The Vicinity of the Heater
Do not store or use flammable objects, liquids or vapors near the heater.
Immediately remove these items if they are present.
Vehicles and Other
Objects
Maintain the clearances to combustibles.
Do not hang anything from, or place anything on, the heater.
Make sure nothing is lodged underneath the reflector, in between the tubes or
in the decorative or protective grilles (included with select models).
Immediately remove objects in violation of the clearances to combustibles.
Reflector
Support reflector with reflector hanger and support strap.
Reflector must not touch tube.
Make sure there is no dirt, sagging, cracking or distortion.
Do not operate if there is sagging, cracking or distortion.
Make sure reflectors are correctly overlapped.
.
Clean outside surface with a damp cloth.
Vent Pipe
Venting must be intact. Using a flashlight, look for obstructions, cracks on the
pipe, gaps in the sealed areas or corrosion.
The area must be free of dirt and dust. Clean as required.
Remove any carbon deposits or scale using a wire brush.
Outside Air Inlet
Inlet must be intact. Look for obstructions, cracks on the pipe, gaps in the
sealed areas or corrosion.
The area must be free of dirt and dust. Clean and reinstall as required.
Tubes
Make sure there are no cracks.
Make sure tubes are connected and suspended securely.
.
Make sure there is no sagging, bending or distortion.
Clean or replace as required.
Gas Line
.
Burner Observation
Window
Make sure it is clean and free of cracks or holes.
Clean and replace as required.
Содержание NDUSTRIA NHE Series
Страница 2: ......
Страница 4: ......
Страница 21: ...SECTION 6 HEATER INSTALLATION 17 FIGURE 16 Linear Heater Layout Overview ...
Страница 22: ...NHE SERIES INSTALLATION OPERATION AND SERVICE MANUAL 18 FIGURE 17 Linear Heater Layout Overview Continued ...
Страница 37: ...SECTION 7 OPTIONAL HEATER ACCESSORIES 33 FIGURE 26 U Tube Heater Layout Overview ...
Страница 38: ...NHE SERIES INSTALLATION OPERATION AND SERVICE MANUAL 34 FIGURE 27 U Tube Heater Layout Overview Continued ...
Страница 69: ...SECTION12 TROUBLESHOOTING 65 ...
Страница 70: ...NHE SERIES INSTALLATION OPERATION AND SERVICE MANUAL 66 12 2 Manifold Gas Pressure Setting Side View of Heater ...
Страница 74: ...NHE SERIES INSTALLATION OPERATION AND SERVICE MANUAL 70 ...
Страница 76: ...NHE SERIES INSTALLATION OPERATION AND SERVICE MANUAL 72 ...
Страница 77: ...SECTION 15 THE NDUSTRIA NHE WARRANTY 73 2020 ...
Страница 78: ...NHE SERIES INSTALLATION OPERATION AND SERVICE MANUAL 74 ...