www.rletech.com
64
970.484.6510
B
Leak Detection Modbus Master
8
Type “2” for configuring the Zone Setup.
9
To configure Input #2, type D2, then press Enter.
10
Press “1” to enable the zone then press Enter.
11
To assign a label to that field type “L2”, then press Enter. You can enter the label desired
for that Slave device. You can enter 15 characters per label, including spaces.
12
Repeat steps 7-9 to configure any remaining slave devices.
13
Once completed configuring the zones, go to the View Zones screen on the local display
(LCD) to view the status.
14
RLE recommends generating alarms from each panel to ensure proper communication.