www.rletech.com
51
970.484.6510
8
Modbus Communication
8.2.
Packet Communications For The LD5100
This section covers the registers, their names, and a brief description of what they refer to.
8.2.1 Function 03: Read Output Registers
To read the LD5100 parameter values, the master must send a Read Output Registers request
packet. The Read Output Registers request packet specifies a start register and the number of
registers to read. The start register is numbered from zero (40001 = zero, 40002 = one, etc).
Table 8.2
Read Output Registers Packet Structure
Read Registers Request Packet
Read Registers Response Packet
Slave Address (1 byte)
Slave Address (1 byte)
03 (Function code) (1 byte)
03 (Function code) (1 byte)
Start Register (2 bytes)
Byte count (1 byte)
# of registers to read (2 bytes)
First register (2 bytes)
Crc Checksum (2 bytes)
Second register (2 bytes)
…
Crc Checksum (2 bytes)
Содержание LD5100
Страница 1: ...Leak Detection LD5100 User Guide...
Страница 8: ...970 484 6510 8 rletech com Notes...
Страница 10: ...970 484 6510 10 rletech com C Preventive Maintenance 65 D Troubleshooting 67 E Technical Specifications 71...
Страница 11: ...970 484 6510 11 rletech com...
Страница 12: ...970 484 6510 12 rletech com Notes...
Страница 14: ...970 484 6510 14 rletech com Notes...
Страница 24: ...www rletech com 24 970 484 6510 2 Connections and Settings Notes...
Страница 30: ...www rletech com 30 970 484 6510 4 4 20mA Output Testing Notes...
Страница 48: ...www rletech com 48 970 484 6510 7 EIA 232 Interface Notes...
Страница 60: ...www rletech com 60 970 484 6510 A Updating Firmware Notes...
Страница 66: ...www rletech com 66 970 484 6510 C Preventive Maintenance Notes...
Страница 70: ...www rletech com 70 970 484 6510 D Troubleshooting Notes...