RKI 65-2437RKSS-05 Скачать руководство пользователя страница 8

 

 4 • 65-2437RKSS-05 CO Detector

Junction Box

The stainless steel, corrosion resistant junction box allows you to install the detector at a 
mounting site that is remote from a controller, and it protects the detector wiring 
connections. Two conduit hubs allow you to mount the detector to the junction box and 
connect the wiring from the detector to a controller. An O-ring seals the interface between 
the junction box cover and the junction box base.

The terminal block within the junction box facilitates the wiring process. A cover on the 
front of the junction box allows access to the interior of the junction box. A locking set 
screw on the junction box cover allows you to secure the junction box cover and prevent it 
from being removed.

Installation

This section describes procedures to mount the CO detector in the monitoring 
environment and wire the detector to a controller.

Mounting the CO Detector

1.

Select a mounting site that is representative of the monitoring environment. Consider 
the following when you select the mounting site.

Select a site where the detector is not likely to be bumped or disturbed. Make sure 
there is sufficient room to perform start-up, maintenance, and calibration 
procedures.

Select a site where the target gas is likely to be found first.

NOTE:

If your application does not require a specific mounting site, mount the detector 
at approximately breathing level.

Содержание 65-2437RKSS-05

Страница 1: ...RKI Instruments Inc www rkiinstruments com 65 2437RKSS 05 Carbon Monoxide Detector Operator s Manual Part Number 71 0439 Revision P1 Released 9 14 17...

Страница 2: ...calibration and maintenance of the detector is essential for proper operation and correct readings Please calibrate and maintain this detector regularly Frequency of calibration depends upon the type...

Страница 3: ...t costs local repair costs transportation costs or contingent expenses incurred without our prior approval THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY AND ALL OTHER WARRANTIES AND REPRESENTATIONS EXPRES...

Страница 4: ...he CO Detector 4 Wiring the CO Detector to a Controller 5 Startup 7 Introducing Incoming Power 7 Setting the Zero Signal 7 Maintenance 8 Preventive Maintenance 8 Troubleshooting 9 Replacing Components...

Страница 5: ...e instructions and warnings in this manual to assure proper and safe operation of the 65 2437RKSS 05 and to minimize the risk of personal injury Be sure to maintain and periodically calibrate the 65 2...

Страница 6: ...on describes the components of the 65 2437RKSS 05 CO detector The 65 2437RKSS 05 consists of the 65 2438 CO detector and junction box Figure 1 CO Detector Component Location Stainless Steel J Box Lock...

Страница 7: ...ntly bonded to the cap Two wires extend from the top of the detector housing body Use these wires to connect the CO detector to the junction box terminal strip The housing includes a four socket patte...

Страница 8: ...the junction box A locking set screw on the junction box cover allows you to secure the junction box cover and prevent it from being removed Installation This section describes procedures to mount th...

Страница 9: ...source is OFF before you make wiring connections 1 Turn off the controller 2 Turn off or unplug power to the controller 3 Remove the junction box cover WARNING To maintain the explosion proof classif...

Страница 10: ...junction box cover to the junction box 7 Route the cable or wires leading from the CO detector through one of the conduit hubs at the controller housing Use appropriate conduit fittings and constructi...

Страница 11: ...the Zero Fresh Air Reading WARNING If the detector installation is explosion proof do not remove the detector housing cap or junction box cover while the circuits are energized unless the area is dete...

Страница 12: ...ble external alarms 2 Verify that the controller display reading for the channel you are testing is 0 If the display reading is not zero set the zero reading of the detector as described in the Start...

Страница 13: ...lt or Unable to Calibrate Detector responds slowly or does not respond during response test Unable to accurately set the zero or response reading during calibration Detector requires frequent calibrat...

Страница 14: ...in the detector housing 8 Make sure the cap gasket is in place and screw the detector housing cap back onto the detector housing body 9 Turn on or plug in power to the controller 10 Turn on the contro...

Страница 15: ...ect 8 Reinstall the junction box cover 9 Turn on or plug in power to the controller 10 Turn on the controller and place into normal operation CAUTION Allow the replacement detector to warm up for 5 mi...

Страница 16: ...he fixed flow regulator to the calibration cup 4 Put the controller into its calibration program Setting the Zero Reading NOTE If you can verify that the CO detector is in a fresh air environment you...

Страница 17: ...regulator from the cylinder 8 Remove the calibration cup from the detector NOTE For convenience leave regulator and calibration cup connected by the sample tubing 9 Allow about 45 seconds for the gas...

Страница 18: ...9 65 2437RKSS 05 CO Detector Operator s Manual this document 81 0064RK Calibration cylinder 50 PPM CO in air 17 liter 81 0064RK 01 Calibration cylinder 50 PPM CO in air 34 liter steel 81 0064RK 03 Cal...