32 • Chapter 4: Display Mode
04 Series for CO(-H2)
Temperature Screen (TEMP)
The
TEMP
screen shows the surrounding area’s temperature.
Alarm Points Screen (ALARM--P)
The Alarm Points Screen shows the gas alarm settings.
1. After entering Display Mode, press and release POWER MODE until the
ALARM--P
screen sequence appears.
2. Press and release AIR. The Full Scale Setting screen appears.
3. Use AIR to scroll through the Warning, Alarm, Alarm H, STEL, and TWA settings.
4. Press and release POWER MODE to return to the Alarm Points Screen.
25C
TEMP
DISP
ALARM-P
DISP
YES / AIR
DISP
NO /MODE
CO
2000
F. S.
ppm
CO
25
WARNING
ppm
CO
50
ALARM
ppm
CO
1200
ALARM H
ppm
CO
200
STEL
ppm
CO
25
TWA
ppm
AIR AIR
AIR AIR
AIR