Appendix A: Relay Operation
AirLink 7032 Gas Monitor Operator’s Manual
Failsafe Setting’s Effect on Normally-Open/Normally-
Closed Contacts
If Failsafe is set to No, the relays are de-energized in normal operation and energize when the
appropriate alarm circuit is activated. The NO (normally open) relay contacts are open during
non-alarm operation and close when the appropriate alarm condition occurs. The NC (normally
closed) relay contacts are closed during non-alarm operation and open when the appropriate alarm
condition occurs.
If Failsafe is set to Yes, the relays are energized in normal operation and de-energize when the
appropriate alarm circuit is activated. The NO (normally open) relay contacts are closed during
non-alarm operation and open when the appropriate alarm condition occurs. The NC (normally
closed) relay contacts are open during non-alarm operation and close when the appropriate alarm
condition occurs.
Figure 14: Relay Circuit Schematic