background image

65-2434RK CO Transmitter • 3

Interconnect Terminal Strip

The interconnect terminal strip is the four-point terminal strip on the lower left side of the 
amplifier PCB. Use the interconnect terminal strip to connect the transmitter to a 
controller.

Sensor Sockets

There are four sensor sockets located in a circular pattern near the top of the amplifier 
PCB. The sensor plugs into these sockets.

Span Pot

The span pot is near the bottom right corner of the amplifier PCB. Use the span pot to 
adjust the transmitter’s response output during the calibration procedure.

Zero Pot

The zero pot is above the span pot. Use the zero pot to adjust the transmitter’s target gas-
free output during the start-up and calibration procedures.

CAUTION:

There is a third potentiometer on the PCB, the null potentiometer. It is factory-set. 
Do not adjust it.

Test Points

The test points (labeled CAL+ and CAL-) are on the right of the interconnect terminal 
strip. The test points produce a 100 - 500 mV output that is proportional to the 
transmitter’s 4 - 20 mA output. Use the test points and a voltmeter to measure the 
transmitter’s output during the start-up and calibration procedures.

Enclosure

The enclosure enables you to install the CO transmitter at a mounting site that is remote 
from the controller. The enclosure also protects the amplifier PCB and wiring connections 
made to the transmitter. Use the cable bushing on the bottom of the enclosure to connect 
wiring from the amplifier PCB to a controller.

Use the enclosure’s two mounting holes, accessible with the cover removed, to mount the 
CO transmitter to a vertical surface at the monitoring site. Use the cover on the front of the 
enclosure to access the interior of the enclosure.

www.

.com

[email protected]

1.800.561.8187

Содержание 65-2434RK

Страница 1: ...65 2434RK Carbon Monoxide Transmitter Operator s Manual Part Number 71 0061RK Revision D Released 2 16 11 www com information itm com 1 800 561 8187...

Страница 2: ...nce of the detector is essential for proper operation and correct readings Please calibrate and maintain this detector regularly Frequency of calibration depends upon the type of use you have and the...

Страница 3: ...costs transportation costs or contingent expenses incurred without our prior approval THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY AND ALL OTHER WARRANTIES AND REPRESENTATIONS EXPRESSED OR IMPLIED AND AL...

Страница 4: ...tter to a Controller 5 Startup 6 Introducing Incoming Power 6 Setting the Zero Signal 6 Maintenance 7 Preventive Maintenance 7 Troubleshooting 8 Replacing Components of the CO Transmitter 9 Calibratio...

Страница 5: ...n using the 65 2434RK you must follow the instructions and warnings in this manual to assure proper and safe operation of the 65 2434RK and to minimize the risk of personal injury Be sure to maintain...

Страница 6: ...Filter The disc shaped charcoal filter is secured to the sensing face of the sensor by a rubber boot The filter prevents interference gases hydrogen sulfide H2S and certain hydrocarbons from producing...

Страница 7: ...null potentiometer It is factory set Do not adjust it Test Points The test points labeled CAL and CAL are on the right of the interconnect terminal strip The test points produce a 100 500 mV output th...

Страница 8: ...maintenance and calibration procedures Select a site where the target gas is likely to be found first NOTE If your application does not require a specific mounting site mount the transmitter at appro...

Страница 9: ...terminal labeled FB CAUTION Leave the shield drain wire insulated and disconnected at the transmitter You will connect the opposite end of the cable s drain wire at the controller 6 Secure the cover...

Страница 10: ...necessary to apply zero air when verifying or setting the fresh air reading The procedure below describes applying zero emission air usually called zero air using a calibration kit that includes a ca...

Страница 11: ...dure describes a test to verify that the CO transmitter responds properly to carbon monoxide NOTE Performing a response test on the CO transmitter may cause alarms Be sure to put the controller into i...

Страница 12: ...ion kit as described in the Calibration section of this insert 7 When the display reading falls below the alarm setpoints return the controller to normal operation Quarterly Calibrate the CO transmitt...

Страница 13: ...er instruction Replacing Components of the CO Transmitter This section includes procedures to replace the CO sensor amplifier PCB and charcoal filter Replacing the Sensor 1 Turn off the controller 2 T...

Страница 14: ...y plug the CO sensor with rubber boot and charcoal filter into the socket pattern on the amplifier PCB NOTE Match the sensor s male pins with the four female sockets as you plug the sensor into the so...

Страница 15: ...present and calibration adjustments are minimal at calibration then a calibration frequency of every 6 months is adequate If an application is very demanding for example if CO is present often and in...

Страница 16: ...ator s on off knob clockwise to close it 9 Remove the calibration cup from the sensor face 10 Unscrew the regulator from the zero air calibration cylinder 11 Leave the sample tubing connected to the r...

Страница 17: ...ts replacement parts and accessories for the CO channel Table 3 Parts List Part Number Description 06 1248RK Sample tubing order by the foot 07 0203RK Retaining boot for filter 33 7101RK Filter charco...

Отзывы: