61-1000RK-05 Combustible Gas Detector• 9
Start Up
This section describes procedures to start up the combustible gas detector and place the
detector into normal operation.
Introducing Incoming Power
1. Complete the installation procedures described earlier in this manual.
2. Verify that the power wiring to the controller is correct and secure. Refer to the
controller instruction manual.
3. Turn on or plug in the incoming power at the power source end, then turn on the
controller.
4. Verify that the controller is on and operating properly. Refer to the controller
instruction manual.
CAUTION:
Allow the detector to warm up for 5 minutes before you continue with the next
section, “Setting the Zero Reading.”
Setting the Zero Reading
CAUTION:
If you suspect the presence of combustible gas in the monitoring environment, use
the zero air calibration cylinder to introduce “fresh air” to the detector and verify an
accurate zero reading.
1. Verify that the detector is in a fresh air environment (environment known to be free of
combustible gas).
2. Verify a reading of 0% LEL at the controller.
If the display reading is 0% LEL, start up is complete. The combustible detector is in
normal operation. If the display reading is not 0% LEL, continue with step 3.
3. Perform a zeroing operation at the controller. See the controller instruction manual for
directions.