61-1000RK-05 Combustible Gas Detector• 13
NOTE:
For convenience, leave the components of the calibration kit connected by the
sample tubing.
4. Allow about 15 seconds for the gas reading to decrease below the alarm points and
then return the controller to normal operation.
NOTE
: If you do not allow the gas reading decrease below the alarm points, then
unwanted alarms may occur.
5. Verify that the controller display reading decreases and stabilizes at 0%LEL.
6. Store the components of the calibration kit in a safe and convenient place.
Parts List
Table 3 lists replacement parts and accessories for the 61-1000RK-05 combustible gas
detector.
Table 3: Parts List
Part Number
Description
18-0400RK-01
Junction box with spacers
61-0140RK-05
Replacement combustible gas detector
71-0087RK
61-1000RK-05 Combustible Gas Detector Operator’s Manual
(this docu-
ment)
81-0007RK-01
Calibration cylinder (50% LEL Hexane in air, 34 liter)
81-0012RK-01
Calibration cylinder (50% LEL Methane in air, 34 liter)
81-0076RK-01
Zero air calibration cylinder (34 liter)
81-1003RK
Regulator, 0.5 liter/minute; continuous flow
(for 17 and 34 liter calibration cylinders)
81-1117RK
Calibration cup