35-3001-01H Hydrogen Sample-Draw Detector • 5

Status LEDs

Two status LEDs are above the flowmeter. They are also visible through the window in the housing 
door. The green Pilot LED is on when the sample-draw detector is receiving power from the 
controller. The red Fail LED is on when the sample flow rate is below the low flow level.

Pressure Switch

The pressure switch is mounted to the back of the flowmeter circuit board. The pressure switch 
monitors the flow rate of the incoming gas sample.

If the flow rate falls below the preset low flow level, the pressure switch causes the Fail LED to 
turn on and interrupts the signal from the detector. The interrupted detector signal causes a fail 
condition at the controller. The low flow level is factory-set at 0.6 SCFH (±0.1 SCFH). See 
“Adjusting the Low Flow Setting” on page 14 to adjust this setting.  

Pump Reset Switch

The pump reset switch is located to the left of the status LEDs. When a low flow condition occurs, 
the pump will be shut off. To reset the low flow condition and start the pump again, press and hold 
the pump reset switch for about 2 seconds, then release. 

Hydrophobic Filter

The hydrophobic filter is located toward the bottom left of the main circuit board. The filter 
prevents particulates and water in the incoming gas sample from damaging the flow and detection 
systems. Replace the filter when it appears dirty, discolored, or clogged.

Pump

The pump is mounted to the right side of the main circuit board. The pump pulls the gas sample 
into the sample-draw detector. The pump operates on 24 VAC, which is generated from the 24 
VDC supplied by the controller.

Hydrogen Sensor

The catalytic hydrogen sensor detects hydrogen in the %LEL range. It uses a catalytic element for 
detection. The reaction of gas with oxygen on the catalyst causes a change in the resistance of the 
element which changes the current flowing through it. The current is proportional to the detection 
range of the sample-draw detector.

The hydrogen sensor is installed in the flow block and the flow block is mounted to the middle of 
the main circuit board. The sensor housing includes a sintered metal flame arrestor on one end that 
allows gas to diffuse into the sensor. The sensor has a built in molecular sieve that only allows 
hydrogen to diffuse into the detector. On the other end, five pins extend from the sensor and plug 
into the socket connector. The connector allows you to replace the sensor without disconnecting the 
wiring. Four leads extending from the connector allow you to connect the hydrogen sensor to the 
main circuit board. 

Содержание 35-3001-01H

Страница 1: ...www rkiinstruments com 35 3001 01H Hydrogen Sample Draw Detector Operator s Manual Part Number 71 0320RK Revision A Released 8 3 17...

Страница 2: ...iodic calibration and maintenance of the detector is essential for proper operation and correct readings Please calibrate and maintain this detector regularly Frequency of calibration depends upon the...

Страница 3: ...placement costs local repair costs transportation costs or contingent expenses incurred without our prior approval THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY AND ALL OTHER WARRANTIES AND REPRESENTATION...

Страница 4: ...Draw Detector to a Controller 8 Start Up 10 Introducing Incoming Power 10 Setting the Zero Reading 10 Maintenance 11 Preventive Maintenance 11 Troubleshooting 12 Replacing Components of the Hydrogen S...

Страница 5: ...and safe operation of the 35 3001 01H and to minimize the risk of personal injury Be sure to maintain and periodically calibrate the 35 3001 01H as described in this manual Table 1 Specifications Tar...

Страница 6: ...nstallation where general purpose equipment is in use B W Hydrogen Sensor Oxygen Sensor Terminal Strip Pump Hydrogen Flow Block B G Detector Amp Terminal Strip Factory Wired Mounting Foot 4X _ O X Y G...

Страница 7: ...ctory installed If the particle filter is installed directly to the inlet fitting the tubing stub must be used If the particle filter is installed somewhere else like at the end of the inlet line the...

Страница 8: ...to the main circuit board See Installation on page 6 for all wiring procedures related to the sample draw detector Flowmeter Circuit Board Connector The flowmeter circuit board connector is a six pos...

Страница 9: ...left of the main circuit board The filter prevents particulates and water in the incoming gas sample from damaging the flow and detection systems Replace the filter when it appears dirty discolored o...

Страница 10: ...owing when you select the mounting site Is there enough room to open the housing door and make wiring and tubing connections at the bottom of the housing Make sure there is sufficient room to perform...

Страница 11: ...components 4 Connect a length of sample tubing to the other side of the particle filter and route it to the sampling area 1 4 O D rigid polypropylene Teflon or flexible polyurethane tubing may be use...

Страница 12: ...t to seal the connection between the tubing and the inlet fitting 3 Hand tighten the nut on the exhaust fitting so the ferrules clamp on the tubing If the tube nut is removed see Figure 5 for the arra...

Страница 13: ...etector to a Controller 9 If shielded cable is used connect the cable s drain wire to an available chassis earth ground at the controller RKI controllers typically have a ground stud that can be used...

Страница 14: ...o test the sample line press and hold the reset switch and plug the open end of the sample line with your thumb If the flowmeter ball drops to the bottom of the flowmeter the incoming sample line is n...

Страница 15: ...ce the response time of this test use a short incoming sample line If the sample draw detector s sample line is long connect a shorter line for this test Make sure you reconnect the sample line after...

Страница 16: ...the sensor flow control valve 2 If you cannot set the correct flow rate check the sample lines for obstructions or kinks 3 Verify that the sensor wiring is correct and secure Wiring the Sample Draw Hy...

Страница 17: ...ining plate then lift the plate connector and sensor out of the housing 5 Unplug the connector from the sensor 6 Verify that you are using the correct replacement sensor NC 6244A is printed on the sen...

Страница 18: ...factory set low flow setting is 0 6 SCFH 0 1 To adjust the low flow setting 1 Use the sensor flow control valve to set the flow to 0 6 SCFH Turn the valve s knob counterclockwise to increase the flow...

Страница 19: ...ome out with the tube nut Be careful not to lose the O ring that may come out with the tubing stub If you do lose the O ring or if it is damaged see Parts List on page 17 for the spare part number 3 P...

Страница 20: ...tion using a demand flow regulator Preparing for Calibration 1 Follow the instructions in the controller s operator s manual for entering calibration mode NOTE If you can verify a fresh air environmen...

Страница 21: ...ple tubing 3 16 ID x 5 16 OD 3 feet for calibration kit 17 2670 Inlet fitting O ring 17 2671 Inlet fitting front ferrule 17 2672 Inlet fitting back ferrule and tube nut 30 1016RK Pump 33 0165RK Hydrop...

Отзывы: