Outputs 

Number of outputs: 

2 points   
(Isolated between input and output, and 
between output and power supply) 

Output type: 

Relay contact: 

250 V AC, 3 A (Resistive load)   

 1a 

contact 

 

Electrical life 300,000 times or more   

 (Rated 

load) 

Voltage pulse: 

0/12 V DC   

 

(Load resistance 600 

 or more) 

Current: 

0 to 20 mA DC, 4 to 20 mA DC 

 

(Load resistance 600 

 or less) 

Voltage: 

0 to 5 V DC, 0 to 10 V DC, 1 to 5 V DC 

 

(Load resistance 1 k

 or more) 

 

„

 

Control action 

Number of controls: 

2 points 

Control method: 

Brilliant PID control 
Reverse action or direct action is 
selectable (Specify when ordering) 

Additional function: 

Autotuning function 
- With output limiter function 
- With output change rate limiter 

 

„

 

Events 

Number of events: 

2 points/channel 

Event type: 

Temperature event: 
 

Deviation high, Deviation low, 

 

Deviation high/low, Band,   

 

Process high, Process low 

 

„

 

Heater break alarm (HBA) function 

Number of HBA: 

2 points 

Setting range: 

0.0 to 100.0 A (0.0 A: OFF) 

Additional function: 

Number of event delay times: 
 

1 to 255 times 

 

„

 

Control loop break alarm (LBA) function 

Number of LBA: 

2 points 

LBA time: 

1 to 7200 seconds 

LBA deadband (LBD) setting: 

0 to Input span 

 

„

 

Program control 

Number of patterns: 

16 pattern max. 
(With pattern link function)

 

Number of segments:  16 segment/pattern max.

 

Time signal output: 

16 point/pattern

 

 

„

 

Communications 

Communication interface: 
 

Based on RS-485, EIA standard

 

Communication protocol: 

RKC communication   
(ANSI X3.28 subcategory 2.5, A4) 
or Modbus

 

 

„

 

Others 

Power supply voltage:  24 V DC

 

Power supply voltage range: 

21.6 V DC to 26.4 V DC

 

Current consumption:  120 mA or less/module

 

Allowable ambient temperature range: 

10 to 

+

50 

°

Allowable ambient humidity range: 

5 to 95 %RH (Non condensing) 
Absolute humidity:   
MAX.W.C 29 g/m

3

 dry air at 101.3 kPa 

Weight: 

Approx. 220 g

 

 
 