![RKC INSTRUMENT X-TIO-A Скачать руководство пользователя страница 4](http://html1.mh-extra.com/html/rkc-instrument/x-tio-a/x-tio-a_instruction-manual_1466707004.webp)
IMS01N02-E4
4
5.3 DIN rail Mounting
Mounting procedures
1.
Pull down the mounting bracket at the bottom of the module
(A). Attach the hooks on the top of the module to the DIN rail
and push the lower section into place on the DIN rail (B).
(B) Push
Mounting
bracket
DIN rail
(A) Pull down
Fig. 1
2.
Slide the mounting bracket up to secure the module to the
DIN rail. (Fig. 2)
Locked
Fig. 2
End Plate mounting
Hold tight both ends of the modules jointed together with the end
plates and then fix the end plates with screws. Even if only one
temperature control module [basic type]
is used, also hold tight
both ends of the module with the end plates.
End Plate
Temperature control module [basic type]
End Plate
Joint connector cover
*
*
For the conservation of the contact of connector, install a joint
connector cover in module of both ends.
Removing procedures
Pull down a mounting bracket with a blade screwdriver (A). Lift
the module from bottom, and take it off (B).
(A) Pull down
(B) Lift and take off
5.4 Panel Mounting
Mounting procedures
1.
Pull down the mounting bracket (A) until locked and that a
mounting hole appears.
2.
Prepare one mounting bracket per module (B) sold
separately (KSRX-55) and then insert it in the rear of the
terminal board at top of the module until locked but a
mounting hole does not disappear.
3.
Mount each module directly on the panel with screws which
are inserted in the mounting holes of the top and bottom
mounting brackets.
Recommended tightening torque: 0.3 N
⋅
m (3 kgf
⋅
cm)
The customer needs to provide the M3 size screws.
Select the screw length that matches the mounting
panel.
(A) Pull down
(B) Insert
(KSRX-55)
Mounting bracket
(Sold separately)
Mounting
holes
130
.5
±
0.
2
35.25
±
0.2 30
±
0.2
M3
Module of 40.5 mm wide
Module of 30 mm wide
Mounting dimensions