background image

  

IMS01P12-E1

 

1. OUTLINE 

The temperature control module for CC-Link V-TIO-L/V-TIO-M can 
send and receive data to/from CC-Link corresponding programmable 
controllers (Mitsubishi Electric

 

PLC: MELSEC) via CC-Link. 

In addition, the V-TIO-L/V-TIO-M module is connected to CC-Link 
as a remote device station. 

 

[The features of V-TIO-L/V-TIO-M module] 

 One module (V-TIO-L or V-TIO-M) enables temperature control 

corresponding to two channels. 

 It has power supply and communication terminals in addition to 

temperature control input and output terminals.   

 One digital input (DI) point and two digital output (DO) points 

can be optionally added. 

  All data are set by communication.

 

 

 

CC-Link 

Measured

input 

Power supply input 

(24 V DC) 

Temperature control 

module for CC-Link 

V-TIO-L/ V-TIO-M 

Control 

output 

Usable modules: 

Temperature control (TIO) module 
[Basic type]: 

V-TIO-A, C 

Temperature control (TIO) module 
[Extension type]: V-TIO-B, D 
(Up to 30 modules)

 

Event input/output 
connector (optional) 

Digital input: 

1 point 

Digital output:  2 points

 

Mitsubishi Electric 

PLC (MELSEC) 

 

 

For details of CC-Link communication, refer to the 

Module 

Type Controller SRV CC-Link Communication 
Instruction Manual (IMS01P13-E

).

 

 

For details when dividing two or more temperature 
control modules into some groups and then installed, 
refer to the 

Module Type Controller SRV CC-Link 

Communication Instruction Manual (IMS01P13-E

)

.

 

 

For communication using host communication terminals, 
refer to the 

Module Type Controller SRV Communication 

Instruction Manual (IMS01P01-E

)

.

 

 
 

2. PRODUCT CHECK 

Before using this product, check each of the following: 

 Model code 

  Check that all of the accessories delivered are complete. 

 Check that there are no scratch or breakage in external 

appearance (case, front panel, terminal, etc). 

V–TIO– 

 

 



 – 

 

 

 

 

 – 

 

 – 

 / Y 

(1) (2) 

(3) 

(4) (5)  (6) (7) (8)  (9) (10)  (11)  (12) 

(1) Type 

L:  Module for CC-Link, Heat control 
M: Module for CC-Link, Heat/Cool control 

 

(2) Control action

 

[For Heat control] 
F:  PID action with autotuning (AT) (reverse action) 
D:  PID action with autotuning (AT) (direct action) 
[For Heat/Cool control] 
B:  Heat/Cool PID action with autotuning (AT) (air cooling) 
W: Heat/Cool PID action with autotuning (AT) (water cooling) 

(3) Input range 

(Each channel common code)

 

[Thermocouple input] 

Type

Code

Range Code 

Range 

K02

0 to 400 

KB9 

32 to 752 

 

K04

0 to 800 

KB8 

32 to 1472 

 K16

200 to 

1372 

C KB7 

328 to 

2501 

F

 

K09

0.0 to 400.0 

KC2 

32.0 to 752.0 

F

 K35

200.0 to 

400.0 

C KC1 

328.0 to 

752.0 

F

J02

0 to 400 

JC2 

32 to 752 

 

J04

0 to 800 

JC1 

32 to 1472 

 J15

200 to 

1200 

C JB9 

328 to 

2192 

F

 

J09

0.0 to 400.0 

JC4 

32.0 to 752.0 

F

 J27

200.0 to 

400.0 

C JC3 

328.0 to 

752.0 

F

T08

0 to 400 

TB9 

32 to 752 

 

T09

0 to 200 

TC1 

32 to 392 

 T16

200 to 

400 

C TB8 

328 to 

752 

 

T06

0.0 to 400.0 

TC3 

32.0 to 752.0 

F

 T19

200.0 to 

400.0 

C TC2 

328.0 to 

752.0 

F

E01

0 to 800 

EA8 

32 to 1472 

 

E02

0 to 1000 

EA7 

32 to 1832 

S05

0 to 1768 

SA6 

32 to 3214 

R06

0 to 1768 

RA6 

32 to 3214 

N02

0 to 1300 

NA6 

32 to 2372 

B03

0 to 1800 

BB1 

32 to 3272 

PL

A02

0 to 1390 

AA6 

32 to 2534 

W5Re/
W26Re

W03

0 to 2300 

WA9 

32 to 4172 

[RTD input] 

Type

Code

Range Code 

Range 

Pt100

D17

0 to 400 

DC5 

32 to 752 

 

D33

0 to 850 

DC4 

32 to 1562 

 

D16

0.0 to 400.0 

DC7 

32.0 to 752.0 

F

 D28

200.0 to 

400.0 

C DC6 

328.0 to 

752.0 

F

JPt100

P17

0 to 400 

PC5 

32 to 752 

 

P23

0 to 600 

PC4 

32 to 1112 

 

P16

0.0 to 400.0 

PC7 

32.0 to 752.0 

F

 P28

200.0 to 

400.0 

C PC6 

328.0 to 

752.0 

F

[Voltage/Current input] 

 Code

Type 

Code  Type 

Voltage

201

0 to 100 mV DC 

401 

0 to 5 V DC 

 

501

0 to 10 V DC 

601 

1 to 5 V DC 

Current

701

0 to 20 mA DC 

801 

4 to 20 mA DC 

(4) Control output (CH1),  (5) Control output (CH2) 

M: Relay contact output   

V:  Voltage pulse output 0/12 V DC 

4:  0 to 5 V DC 

5:  0 to 10 V DC 

6:  1 to 5 V DC 

7:  0 to 20 mA DC 

8:  4 to 20 mA DC 

(6) Event input (DI)    [Optional] 

N: None 

1:  Control RUN/STOP 

2:  Event interlock release 

(7) (8)  Event output 1 (DO1)    [Optional] * 
(9) (10) Event output 2 (DO2)    [Optional] * 

[Code of (7)] 
N: None 

1: Channel 1 

[Code of (9)] 
N: None 

2: Channel 2 

[Code of (8) and (10)] 
N: None 

A: Deviation high 

B: Deviation low 

C: Deviation high/low 

D: Band 

E: Deviation high with hold action 

F: Deviation low with hold action 

G: Deviation  high/low  with  hold action  H: Process high 
J:  Process low 

K: Process high with hold action 

L:  Process low with hold action 
Q: Deviation high with re-hold action 
R: Deviation low with re-hold action 
T: Deviation high/low with re-hold action 
P: Heater break alarm (HBA) 

1:  Control loop break alarm (LBA) 

2: Burnout 

3: Temperature rise completion 

  (11) CT type 

(Each channel common code)

 

P: CTL-6-P-N 

S: CTL-12-S56-10L-N 

(12) Version symbol 

No code: For Japanese domestic market   
/Y: For 

International 

market 

 

*  When “N” is selected in (7) or (9), (8) or (10) becomes “N.” 

 

 

 

Содержание V-TIO-L

Страница 1: ...to avoid electric shock by operating personnel All precautions described in this manual should be taken to avoid damage to the instrument or equipment All wiring must be in accordance with local codes and regulations All wiring must be completed before power is turned on to prevent electric shock instrument failure or incorrect action The power must be turned off before repairing work for input br...

Страница 2: ... 0 to 400 C KB9 32 to 752 F K04 0 to 800 C KB8 32 to 1472 F K16 200 to 1372 C KB7 328 to 2501 F K09 0 0 to 400 0 C KC2 32 0 to 752 0 F K35 200 0 to 400 0 C KC1 328 0 to 752 0 F J J02 0 to 400 C JC2 32 to 752 F J04 0 to 800 C JC1 32 to 1472 F J15 200 to 1200 C JB9 328 to 2192 F J09 0 0 to 400 0 C JC4 32 0 to 752 0 F J27 200 0 to 400 0 C JC3 328 0 to 752 0 F T T08 0 to 400 C TB9 32 to 752 F T09 0 to...

Страница 3: ...flashing 1 second cycle RUN When normally for internal communication A green lamp turns on When abnormally for internal communication A green lamp is flashing 0 5 seconds cycle In validation of the module which it connected just after the power is turned on A green lamp is flashing 0 1 seconds cycle When CC Link communication stopped state A green lamp turns off SD During CC Link data send A green...

Страница 4: ...e rotary switch which there is on the left side of module select communication speed for CC Link For this setting use a small slotted screwdriver Setting range 0 to 4 Factory set value 0 Communication speed setting switch Left side view CC Link side Communication speed and maximum transmitter distance maximum length of Network Use CC Link dedicated cable Ver 1 10 Communication speed setting Commun...

Страница 5: ...ecting device for the equipment 5 2 Dimensions Unit mm 6 8 40 5 110 125 78 5 8 2 The above figure shows when provided with the event input output connector but the same also when not provided with the connector 5 3 DIN rail Mounting Mounting procedures 1 Pull down the mounting bracket at the bottom of the module A Attach the hooks on the top of the module to the DIN rail and push the lower section...

Страница 6: ...60950 1 A suitable power supply should be considered in the end use equipment The power supply must be in compliance with a limited energy circuits maximum available current of 8 A In the maximum configuration extension up to 31 modules the 24 V DC supplied equipment may draw up to 4 A The power supply shall be capable of delivering at least 4 A Use the solderless terminal appropriate to the screw...

Страница 7: ...iation URL http www cc link org Connection diagram CC Link dedicated cable Ver 1 10 CC Link dedicated cable Ver 1 10 DA DB DG SLD FG DA DB DG SLD FG DA DB DG SLD FG V TIO L V TIO M module Master station V TIO L V TIO M module TR Terminating resistor 110 5 1 2 W TR TR Always connect a terminating resistor between the DA and DB terminals of the module to be located at the far end 6 4 Event Input Out...

Страница 8: ...ctable Specify when ordering Additional function Autotuning function Events Number of events 2 points channel Event type Temperature event Deviation high Deviation low Deviation high low Band Process high Process low Heater break alarm HBA Control loop break alarm LBA Burnout Temperature rise completion Heater break alarm HBA function Number of HBA 2 points Setting range 0 0 to 100 0 A 0 0 A OFF A...

Отзывы: