5.4 Panel Mounting 

 

Mounting procedures 

1. 

Pull down the mounting bracket (A) until locked and that a 
mounting hole appears. 

2. 

Prepare one mounting bracket per module (B) sold 
separately (KSRX-55) and then insert it in the rear of the 
terminal board at top of the module until locked but a 
mounting hole does not disappear. 

3. 

Mount each module directly on the panel with screws which 
are inserted in the mounting holes of the top and bottom 
mounting brackets. 

Recommended tightening torque: 0.3 N

m (3 kgf

cm) 

 

The customer needs to provide the M3 size screws. 
Select the screw length that matches the mounting 
panel. 

 

(A) Pull down 

(B) Insert 

Mounting bracket 

(Sold separately) 

Mounting 

holes 

[KSRX-55] 

 

 

 

130

.5

 

±

 0.

35.25 

±

 0.2

30 

±

 0.2 

M3 

(Unit: mm)

Module of 40.5 mm wide 

Module of 30 mm wide 

 

 

5.5 Jointing Each Module 

Up to 30 modules (V-TIO-A, V-TIO-B, V-TIO-C or /V-TIO-D) can 
be connected to one module (V-TIO-J or V-TIO-K).

 

Joint these 

modules according to the following procedure. 

 

 

Jointing procedures 

1. 

Mount the modules on the DIN rail and then joint these 
modules together with the joint connector while sliding the 
relevant module. 

2. 

Lift each of the joint tabs located at the top and bottom of the 
module and then insert it in the slot of the adjacent module to 
fix these two modules. 

 

For panel mounting, first joint each module and then 
mount it on the panel. 

 

Joint tab 

Joint connector

When viewed 
from top 

There is one joint tab at each 
of the top and bottom of on 
module. Therefore, fix two 
adjacent modules with these 
two joint tabs. 

Joint tab 
insertion slot

 

 

6. WIRING 

 
 
 
 
 
 

 

6.1 Wiring Cautions 

 

For thermocouple input, use the appropriate compensation 
wire.

 

 

For RTD input, use low resistance lead wire with no 
difference in resistance between the three lead wires.

 

 

To avoid noise induction, keep input signal wire away from 
instrument power line, load lines and power lines of other 
electric equipment.

 

 

If there is electrical noise in the vicinity of the instrument that 
could affect operation, use a noise filter.

 

  Shorten the distance between the twisted power supply wire 

pitches to achieve the most effective noise reduction.

 

 Always install the noise filter on a grounded panel.  

Minimize the wiring distance between the noise filter output 
and the instrument power supply terminals to achieve the 
most effective noise reduction.

 

 Do not connect fuses or switches to the noise filter output 

wiring as this will reduce the effectiveness of the noise filter.

 

 

Power supply wiring must be twisted and have a low voltage 
drop.

 

 

For an instrument with 24 V power supply, supply power from 
a SELV circuit.

 

 

6.2 Terminal Configuration 

 

CT1

T/R(B)

SG

T/R(A)

RS-485

Internal communication

or 

Host communication   

CT input 

Control output 1 

Control output 2

15

Relay contact 

NO 

OUT1 

Voltage pulse/ 

Current/ 

Voltage 

OUT1 

+

 

 

3

6

7

16

17

+

24 V

DC

Power supply

Ground

Thermocouple 

TC1 

+

 

 

Input channel 1 

Voltage/ 

Current 

IN1 

+

 

 

RTD 

RTD1 

A

NO

OUT2

OUT2

+

4

1

4

1

10

13

10

14

13

13

10

TC2

+

 

IN2

+

 

12

8

12

12

RTD2

B

B

A

9

Input channel 2

19

18

20

FG

16 15  3 

17  7 

20 19  14  13  12 

18  11  10  9 

Upper-side terminal

CT2

Relay contact

Voltage pulse/

Current/ 

Voltage 

Lower-side terminal

Thermocouple

RTD

Voltage/ 

Current 

Voltage/

Current 

 

 

 

For heat/cool PID control (V-TIO-K), input channel 2 
becomes unused. 

 

For heat/cool PID control (V-TIO-K), Control output 
(CH1) corresponds to the heating output and 
Control output (CH2) corresponds to the cooling 
output. 

 

Mounting 
dimensions 

 

 

 

 

To prevent electric shock or instrument failure, do not 
turn on the power until all the wiring is completed. 

!

WARNING 

5.9 mm or less

3.2 mm or more

Recommended tightening torque:

 

0.4 N

m (4 kgf

cm) 

 

Содержание V-TIO-J

Страница 1: ...panel All high voltage connections such as power supply terminals must be enclosed in the instrumentation panel to avoid electric shock by operating personnel All precautions described in this manual...

Страница 2: ...K K02 0 to 400 C KB9 32 to 752 F K04 0 to 800 C KB8 32 to 1472 F K16 200 to 1372 C KB7 328 to 2501 F K09 0 0 to 400 0 C KC2 32 0 to 752 0 F K35 200 0 to 400 0 C KC1 328 0 to 752 0 F J J02 0 to 400 C J...

Страница 3: ...idly NS or NET Network status Network is operating normally but communications have not yet been established A green lamp flashes Network is operating normally communications established A green lamp...

Страница 4: ...ommunication mode selection OFF DeviceNet communication mode ON Host communication RS 485 mode Factory set value DeviceNet communication mode Switch No 3 OFF fixed Don t change this one Switch No 8 OF...

Страница 5: ...igure of micro style connector type is the same as a open style connector type Depth in connector mounting Conduct installation in consideration of the sizes of the connector and cable when connector...

Страница 6: ...esistance between the three lead wires To avoid noise induction keep input signal wire away from instrument power line load lines and power lines of other electric equipment If there is electrical noi...

Страница 7: ...Number of inputs 2 points Isolated between each channel Thermocouple input Voltage low input Not isolated between each channel RTD input Voltage high input Current input Input type Thermocouple K J T...