RKC INSTRUMENT V-TIO-J Скачать руководство пользователя страница 5

 

IMS01P10-E1

 

5

 

5. MOUNTING 

 
 
 
 
 
 

 

5.1 Mounting Cautions 

(1) This instrument is intended to be used under the following 

environmental conditions. 

(IEC61010-1)

   

[OVERVOLTAGE CATEGORY II, POLLUTION DEGREE 2]

 

(2)  Use this instrument within the following ambient temperature 

and ambient humidity. 

• 

Allowable ambient temperature: 

10 to 

+

50 

°

• 

Allowable ambient humidity: 

5 to 95 % RH 

(Absolute humidity: MAX.W.C 29 g/m

3

 dry air at 101.3 kPa) 

(3)  Avoid the following when selecting the mounting location.

 

• 

Rapid changes in ambient temperature, which may cause 
condensation. 

• 

Corrosive or inflammable gases. 

• 

Direct vibration or shock to the mainframe. 

• 

Water, oil, chemicals, vapor or steam splashes. 

• 

Excessive dust, salt or iron particles. 

• 

Excessive induction noise, static electricity, magnetic fields or 
noise. 

• 

Direct air flow from an air conditioner. 

• 

Exposure to direct sunlight. 

• 

Excessive heat accumulation. 

(4) Mounting consideration  

• 

Install the module 200 mm away from the main power line. 

• 

Ensure at least 50 mm space on top and bottom of the control 
unit for maintenance and environmental reasons. 

 

5.2 Dimensions 

 

110

 

6.8

 

40.5

12

5

 

78

 

5

(Unit: mm)

 

 

 

The above figure is open-style connector type. The 
figure of micro-style connector type is the same as a 
open-style connector type. 

 

 

Depth in connector mounting

 

Conduct installation in consideration of the sizes of the 
connector and cable when connector-connected. 

 

110

 

[Usage example of micro-style connector

]

 

(Unit: mm)

Approx. 100 *

 

* For open-style 

connector:  

Approx. 50 mm 

 

 

5.3 DIN rail Mounting 

 

Mounting procedures 

1. 

Pull down the mounting bracket at the bottom of the module 
(A). Attach the hooks on the top of the module to the DIN rail 
and push the lower section into place on the DIN rail (B).   

 

(B) Push

Mounting 

bracket

DIN rail

(A) Pull down 

 

 

2. 

Slide the mounting bracket up to secure the module to the 
DIN rail. 

 

Locked 

 

 

 

 

End Plate mounting 

Hold tight both ends of the modules jointed together with the end 
plates and then fix the end plates with screws. Even if only one 
V-TIO-J/V-TIO-K module is used, also hold tight both ends of the 
module with the end plates. 

 

End Plate

V-TIO-J/V-TIO-K module 

End Plate

Joint connector cover 

*

 

 

 

For the conservation of the contact of connector, install a joint 
connector cover in module of both ends.

 

 

 

Removing procedures 

Pull down a mounting bracket with a blade screwdriver (A). Lift 
the module from bottom, and take it off (B). 

 

(A) Pull down 

(B) Lift and take off 

 

 

 

 

 
To prevent electric shock or instrument failure, 
always turn off the power before mounting or 
removing the instrument. 

!

 

WARNING 

 

Содержание V-TIO-J

Страница 1: ...panel All high voltage connections such as power supply terminals must be enclosed in the instrumentation panel to avoid electric shock by operating personnel All precautions described in this manual...

Страница 2: ...K K02 0 to 400 C KB9 32 to 752 F K04 0 to 800 C KB8 32 to 1472 F K16 200 to 1372 C KB7 328 to 2501 F K09 0 0 to 400 0 C KC2 32 0 to 752 0 F K35 200 0 to 400 0 C KC1 328 0 to 752 0 F J J02 0 to 400 C J...

Страница 3: ...idly NS or NET Network status Network is operating normally but communications have not yet been established A green lamp flashes Network is operating normally communications established A green lamp...

Страница 4: ...ommunication mode selection OFF DeviceNet communication mode ON Host communication RS 485 mode Factory set value DeviceNet communication mode Switch No 3 OFF fixed Don t change this one Switch No 8 OF...

Страница 5: ...igure of micro style connector type is the same as a open style connector type Depth in connector mounting Conduct installation in consideration of the sizes of the connector and cable when connector...

Страница 6: ...esistance between the three lead wires To avoid noise induction keep input signal wire away from instrument power line load lines and power lines of other electric equipment If there is electrical noi...

Страница 7: ...Number of inputs 2 points Isolated between each channel Thermocouple input Voltage low input Not isolated between each channel RTD input Voltage high input Current input Input type Thermocouple K J T...

Страница 8: ...nnection T branch connection Terminating resistor 121 1 4 W is necessary Communication speed 125 kbps 250 kbps or 500 kbps Error control CRC error Node address MAC ID duplication check Maximum number...

Отзывы: