1. OUTLINE
The temperature control module for DeviceNet V-TIO-J/V-TIO-K
can send and receive data to/from DeviceNet compatible
programmable controller (PLC) by the DeviceNet that is a
multi-vendor compatible open field network.
One V-TIO-J/V-TIO-K module enables temperature control
corresponding to two channels. It has power supply and
communication terminals in addition to temperature control input
and output terminals.
All data are set by communication.
Master
Control output
Measured
input
Power supply
(24 V DC)
Usable modules:
•
Temperature control module
[Basic type]:
V-TIO-A/V-TIO-C
•
Temperature control module
[Extension type]: V-TIO-B/V-TIO-D
(Up to 30 modules)
DeviceNet
Temperature control
module for DeviceNet
V-TIO-J/V-TIO-K
Programmable
controller (PLC)
Slave
For details when dividing two or more temperature
control modules into some groups and then installed,
see the
Module Type Controller SRV DeviceNet
Communication Instruction Manual (IMS01P11-E )
.
For details, see the
Module Type Controller SRV
DeviceNet
Communication Instruction Manual
(IMS01P11-E )
.
For host communication using host communication
terminals, see the
Appendix B of
Module Type
Controller SRV DeviceNet Communication
Instruction Manual (IMS01P11-E )
and the
Module
Type Controller SRV Communication Instruction
Manual (IMS01P01-E )
.
2. PRODUCT CHECK
Before using this product, check each of the following:
•
Model code
•
Check that all of the accessories delivered are complete.
•
Check that there are no scratch or breakage in external
appearance (case, front panel, or terminal, etc).
V–TIO–
– N N N – N N – –
(1) (2) (3)
(4) (5)
(6) (7)
(1) Type
J: Module for DeviceNet, heat control
K: Module for DeviceNet, heat/cool control
(2) Control action
(Each channel common code)
[For heat control]
F: PID action with autotuning (AT) (reverse action)
D: PID action with autotuning (AT) (direct action)
[For heat/cool control]
B: Heat/cool PID action with autotuning (AT) (air cooling)
W: Heat/cool PID action with autotuning (AT) (water cooling)
(3) Input range
(Each channel common code)
[Thermocouple input]
Type
Code
Range Code
Range
K
K02
0 to 400
°
C
KB9
32 to 752
°
F
K04
0 to 800
°
C
KB8
32 to 1472
°
F
K16
−
200 to
+
1372
°
C KB7
−
328 to
+
2501
°
F
K09
0.0 to 400.0
°
C
KC2
32.0 to 752.0
°
F
K35
−
200.0 to
+
400.0
°
C KC1
−
328.0 to
+
752.0
°
F
J
J02
0 to 400
°
C
JC2
32 to 752
°
F
J04
0 to 800
°
C
JC1
32 to 1472
°
F
J15
−
200 to
+
1200
°
C JB9
−
328 to
+
2192
°
F
J09
0.0 to 400.0
°
C
JC4
32.0 to 752.0
°
F
J27
−
200.0 to
+
400.0
°
C JC3
−
328.0 to
+
752.0
°
F
T
T08
0 to 400
°
C
TB9
32 to 752
°
F
T09
0 to 200
°
C
TC1
32 to 392
°
F
T16
−
200 to
+
400
°
C TB8
−
328 to
+
752
°
F
T06
0.0 to 400.0
°
C
TC3
32.0 to 752.0
°
F
T19
−
200.0 to
+
400.0
°
C TC2
−
328.0 to
+
752.0
°
F
E
E01
0 to 800
°
C
EA8
32 to 1472
°
F
E02
0 to 1000
°
C
EA7
32 to 1832
°
F
S
S05
0 to 1768
°
C
SA6
32 to 3214
°
F
R
R06
0 to 1768
°
C
RA6
32 to 3214
°
F
N
N02
0 to 1300
°
C
NA6
32 to 2372
°
F
B
B03
0 to 1800
°
C
BB1
32 to 3272
°
F
PL
Ⅱ
A02
0 to 1390
°
C
AA6
32 to 2534
°
F
W5Re/
W26Re
W03
0 to 2300
°
C
WA9
32 to 4172
°
F
[RTD input]
Type
Code
Range Code
Range
Pt100
D17
0 to 400
°
C
DC5
32 to 752
°
F
D33
0 to 850
°
C
DC4
32 to 1562
°
F
D16
0.0 to 400.0
°
C DC7
32.0 to 752.0
°
F
D28
−
200.0 to
+
400.0
°
C DC6
−
328.0 to
+
752.0
°
F
JPt100
P17
0 to 400
°
C
PC5
32 to 752
°
F
P23
0 to 600
°
C
PC4
32 to 1112
°
F
P16
0.0 to 400.0
°
C
PC7
32.0 to 752.0
°
F
P28
−
200.0 to
+
400.0
°
C PC6
−
328.0 to
+
752.0
°
F
[Voltage/current input]
Code
Type
Code Type
Voltage
201
0 to 100 mV DC
401
0 to 5 V DC
501
0 to 10 V DC
601
1 to 5 V DC
Current
701
0 to 20 mA DC
801
4 to 20 mA DC
(4) Control output (CH1), (5) Control output (CH2)
M: Relay contact output V: Voltage pulse output 0/12 V DC
4: 0 to 5 V DC
5: 0 to 10 V DC
6: 1 to 5 V DC
7: 0 to 20 mA DC
8: 4 to 20 mA DC
(6) CT type
(Each channel common code)
P: CTL-6-P-N (for 0 to 30 A)
S: CTL-12-S56-10L-N (for 0 to 100 A)
(7) DeviceNet connector type
N: Open-style connector (Unshielded type)
1: Micro-style connector (Shield type)
For heat/cool PID control (V-TIO-K), input channel 2
becomes unused.
For heat/cool PID control (V-TIO-K), Control output
(CH1) corresponds to the heating output and
Control output (CH2) corresponds to the cooling
output.
Heater break alarm function can not be used when
control output is voltage/current output.
If any of the products are missing, damaged, or if your
manual is incomplete, please contact RKC sales office
or the agent.
*
Accessories
Floppy disk (EDS file)................................................. 1
End Plate.................................................................... 2
Joint connector cover ................................................. 2
Instruction Manual (IMS01P10-E1)............................ 1