6. MODBUS COMMUNICATION PROTOCOL
IMR01J08-E1
47
Continued from the previous page.
(Attribute
RO: Read only, R/W: Read and Write)
Resister
address
Name
Hexa-
decimal Decimal
Attrib-
ute
Data range
Factory set
value
Alarm 2 timer unit
0043 67
Note 1 0 to 60 (sec)
0
Limit action type
selection
0044 68
Note 1 0: Limit action [high limit]
1: Limit action [low limit]
0
Limit action
differential gap
0045 69
Note 1 0 (0.0) to Span
Temperature
input:
2 (2.0)
°
C [
°
F]
Voltage/current
inputs:
0.2 % of span
Limit action hold
action
0046 70
Note 1 0: Without alarm hold action
1: Effective when the power is turned
on
0
Limit action
process
abnormality action
selection
0047 71
Note 1 0: Normal processing
1: Turn the alarm output ON
0
Limit action at the
time of power ON
0048 72
Note 1 0: Limit action output turned O
FF
at
the time of power ON
1
: Limit action output turned O
N
at
the time of power ON
1
<RST key
operation time
selection
0049 73
Note 1 0: Press for one second
1: Press once
1
Reset action
selection
004A 74
Note 1 0: All data is reset with each
monitoring
screen
1: Each data is reset with each
monitoring
screen
0
Limit action release
signal selection
004B 75
Note 1 0: The limit action release signal reset
at the limit action release “0”.
1: The limit action release signal reset
at the limit action release “1”.
0
Note 1: Attribute varies depending on the Engineering mode (Resister address: 0030H) setting.
Continued on the next page.