6. MODBUS COMMUNICATION PROTOCOL
IMR01J08-E1
44
Initial setting data
The initial setting data items can be set by changing to the engineering mode. Transfer to engineering
mode sets “1: Read/Write” with resister address “0030H.”
(Attribute
RO: Read only, R/W: Read and Write)
Resister
address
Name
Hexa-
decimal Decimal
Attrib-
ute
Data range
Factory set
value
Engineering mode
0030 48
R/W Engineering mode setting data items
0: Read only
1: Read/Write
0
Monitor display
configuration
0031 49
Note 1 0: PV/SV display
1: Only PV display
2: Only SV display
0
Input type selection
0032 50
Note 1 0: Thermocouple K
1: Thermocouple J
2: Thermocouple R
3: Thermocouple S
4: Thermocouple B
5: Thermocouple E
6: Thermocouple N
7: Thermocouple T
8: Thermocouple W5Re/W26Re
9: Thermocouple PLII
10: Thermocouple U
11: Thermocouple L
12: RTD Pt100
13: RTD JPt100
14: Voltage 0 to 5 V DC
(Current 0 to 20 mA DC) *
15: Voltage 1 to 5 V DC
(Current 4 to 20 mA DC) *
16: Voltage 0 to 10 V DC
* For the current input specification, a resistor
of
250
Ω
must be connected between
the input terminals.
Note 2
Note 1: Attribute varies depending on the Engineering mode (Resister address: 0030H) setting.
Note 2: Factory set value varies depending on the instrument specification.
Continued on the next page.
The Initial setting data (Engineering mode) should be set according to the
application before setting any parameter related to operation. Once the Initial
setting data is set correctly, those data is not necessary to be changed for the
same application under normal conditions. If they are changed unnecessarily, it
may result in malfunction or failure of the instrument. RKC will not bear any
responsibility for malfunction or failure as a result of improper changes in the
Initial setting.
WARNING
!