5. RKC COMMUNICATION PROTOCOL
IMR01J08-E1
23
Continued from the previous page.
(Attribute
RO: Read only, R/W: Read and Write)
Name Iden-
tifier
Data range
Factory set
value
Attribute
Alarm 1 timer
TD
0 to 9999
R/W
1
Alarm 2 set value
A2
Process alarm, SV alarm:
Same as input range
Deviation alarm:
−
Span to +Span
However, within
−
1999 to +9999 digits
Temperature
input: 50 (50.0)
Voltage/current
inputs: 5.0
R/W
2
Alarm 2 timer
TG
0 to 9999
0
R/W
3
PV bias
PB
−
Span to +Span
However, within
−
1999 to +9999 digits
Temperature
input: 0 (0.0)
Voltage/current
inputs: 0.0
R/W
PV ratio
PR
0.500 to 1.500
1.000
R/W
Digital filter
F1
0 to 100 seconds (0: OFF)
0
R/W
Analog output
selection
4
LA
0: Measured value (PV)
1: Set value (SV)
2: Deviation
0 Note
1
Analog output scale
high
4, 5
HV
Measured value (PV), Set value (SV):
Same as input range
Deviation:
−
Span to +Span
Temperature
input:
Input range
(high limit)
Voltage/current
inputs: 100.0
Analog output scale
low
4, 5
HW
Temperature
input:
Input range
(low limit)
Voltage/current
inputs: 0.0
1
If Alarm 1 is not provided or Alarm 1 timer unit is set to 0, the attribute becomes RO.
2
If Alarm 2 is not provided, the attribute becomes RO.
3
If Alarm 2 is not provided or Alarm 2 timer unit is set to 0, the attribute becomes RO.
4
These communication items, LA, HV and HW are not sent by Acknowledgement ACK from the
host computer. Send the polling sequence for these items separately (Example: EOT 00 LA ENQ).
5
The setting range is from
−
1999 to +9999 regardless of the position of the decimal point.
Note 1 Set the attribute to R/W (Read and Write) for OUT1 when OUT1 is used as transmission output.
Set the attribute to RO (Read only) for OUT1 when OUT1 is not used as transmission output.
Continued on the next page.