5. LADDER COMMUNICATION
IM9000F02-E2
40
5.1.4 Data write
Writes the specified data in the specified identifier. Write data is specified by 4-digit BCD data
excluding the sign data and decimal point.
The number of data which can be written at a time is 1.
PLC send data
Number of bytes
1
1
2
2
2
1
1
Number of BCD
digits
2
2
4
4
4
2
2
Details
STX
(02H)
Device
address
(ADR)
Identifie
r
(ID)
0010
or
0011
dddd
CR
(0DH)
LF
(0AH)
Command
Setting data
(CMD)
REX-F9000 response
Number of bytes
1
1
2
2
2
1
1
Number of BCD
digits
2
2
4
4
4
2
2
Details
STX
Device
address
(ADR)
Identifie
r
(ID)
0010
or
0011
dddd
CR
LF
The original data is returned by ignoring data write for either of the following cases.
z
The data range is exceeded, or
z
a write inhibit identifier is specified.