4. RKC STANDARD COMMUNICATION
IM9000F02-E2
31
4.2 Communication identifier
Communication identifier list
Before changing data corresponding to the identifiers from "XI (input type)" to "WB (alarm 2
hold action selection)," always turn the "Control RUN/STOP" mode to "STOP."
The number of digits is 7 for all data. [Except for model code (ID)]
(Attributes
RO: Read only, R/W: Read/Write)
Name
Iden-
tifier
Data range
Attribute
Factory set
value
Model code
ID
----
RO
----
Measured value (PV)
M1
----
RO
----
Alarm 1 output
*
1
AA
0: OFF 1: ON
RO
----
Alarm 2 output
*
2
AB
0: OFF 1: ON
RO
----
Manipulated output value
(MV)
O1
-5.0 to +105.0%
RO
----
Burnout
B1
0: OFF 1: ON
RO
----
Error code
ER
0 to 255 *
3
RO
----
PID/AT transfer
G1
0 : PID 1 : AT
R/W
0
AUTO/MANUAL
transfer
J1
0 : AUTO
1 : MANUAL
R/W
0
Control RUN/STOP
SR
0 : RUN 1 : STOP
R/W
0
Set value (SV)
S1
Setting limiter (low limit) to
setting limiter (high
limit)
R/W
0.000
Alarm 1 setting
A1
Process alarm :
0.000 to 50.000
q
C
R/W
5.000
Alarm 2 setting
A2
Deviation alarm :
-19.999 to +19.999
q
C
Proportional band
P1
0.001 to 50.000
q
C
* 0.000 can't be set.
R/W
30.000
Integral time
I1
0.1 to 3600.0 sec
* 0.0 can't be set.
R/W
240.0
R/W
Derivative time
D1
0.0 : Derivative action OFF
0.1 to 3600.0 sec
60.0
Continued on the next page.