7.3 Initial Setting Menu 

Display flowcharts in Initialization mode are shown in the following. 

 

Do  not  change  to  the            section parameters and any parameter  in 
the  Initialization  mode  which  is  not  described  in  the  initial  setting 
menu below. It may result in malfunction or failure of the instrument.

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 
 
 

 
7.4 Input Type Selection (SL1) 

When any parameter setting is changed in the Initialization mode, 
check all parameter set values in SV setting mode and Parameter 
setting mode. 

Factory set value varies depending on the input type. 

Set value 

Input type

Hardware

0000 

Thermocouple

 

(TC) 

0001 

0010 

0011 

0100 

0111 

1000 

1001 

1010 

W5Re/W26Re 

1011 

PL II 

0101 

0110 

1100 

Pt100 (JIS/IEC) 

RTD 

1101 

JPt100 (JIS) 

1110 

0 to 5 V DC 

Voltage 

1111 

1 to 5 V DC 

1110 

0 to 20 mA DC 

Current 

1111 

4 to 20 mA DC 

 

Conduct setting so as to meet the instrument specification (input type). 
Setting  change  between  different  symbols  may  cause  malfunction, 
but  the  setting  can  be  changed  when  hardware  types  have  the  same 
symbol.  However,  when  the  setting  is  changed,  always  reset  “SLH” 
and “SLL” (Refer to page 8).

 

  Change Settings 

Example: Change the input type from “K” to “J” 
1.  
Press the SET key. The display will go to SL1. 
 
 
 
2.  Press the UP key to change the number to 1. 
 
 
 
3.  Press the SET key to store the new set value. 

The display goes to the next parameter. 

 

7.5 Temperature Unit and Cooling Type 
 

Selection (SL2) 

Inappropriate settings may result in malfunction. Control type between 
Heat Only and Heat/Cool cannot be changed by this parameter. 

 

Factory set value varies depending on the instrument specification. 

Set 

value

 

Description

 

Temperature 

unit 

Cooling type selection 

0000 

Air cooling (A type) or Heat only type (F, D type)

0001 

Air cooling (A type) or Heat only type (F, D type)

0010 

Water cooling (W type) 

0011 

Water cooling (W type) 

 

  Change Settings 

Example:  Change the temperature unit of the Heat only type 
 

from “ C (0000)” to “ F (0001)” 

1. 

Press the SET key until SL2 is displayed. 

2. 

Press the UP key to change the number to 1. 

 

SV

PV

SV 

PV 

 

3. 

Press  the  SET  key  to  store  the  new  set  value.  The  display  goes  to  the 
next parameter. 

 

7.6  Alarm 1 [ALM1] Type Selection (SL4) 

Alarm 2 [ALM2] Type Selection (SL5) 

If the alarm function is not provided with the instrument when shipped from the 
factory, no alarm output is available by changing SL4 and/or SL5. 

 

SL4 is set to 0000 in the following cases. 

  When the instrument does not have ALM1 output 
  When Control Loop Break Alarm (LBA) is provided and assigned 

to ALM1 

 

SL5 is set to 0000 in the following cases. 

  When the instrument does not have ALM2 output 
  When Control Loop Break Alarm (LBA) is provided and assigned 

to ALM2 

  When the SV alarm is provided and assigned to ALM2 

 

When the Heater Break Alarm (HBA) is provided

 

 

Factory set value varies depending on the instrument specification. 

Set value

Details of setting 

0000

No alarm

0001

Deviation high alarm 

0101

Deviation low alarm

0010

Deviation high/low alarm 

0110

Band alarm

0011

Process high alarm

0111

Process low alarm

1001

Deviation high alarm with hold action * 

1101

Deviation low alarm with hold action * 

1010

Deviation high/low alarm with hold action * 

1011

Process high alarm with hold action * 

1111

Process low alarm with hold action * 

* Hold action: 
When  Hold  action  is  ON,  the  alarm  action  is  suppressed  at  start-up  or  the 
control set value change until the measured value enters the non-alarm range. 

 

 Alarm action type 

Both of the Alarm 1 and Alarm 2 outputs of this instrument are turned on when 
burnout occurs regardless of any of the following actions taken (High alarm, low 
alarm,  etc.).  In  addition,  when  used  for  any  purposes  other  than  these  alarms 
(event, etc.), specify the Z-124 specification (not to be forcibly turned on). 

 

(      : SV        : Alarm set value 

: Alarm differential gap) 

Deviation high alarm 

Deviation high/low alarm 

Deviation low alarm 

(Alarm set value is less than 0.) 

(Alarm set value is less than 0.) 

Low

High

OFF 

ON 

PV 

OFF 

ON 

PV 

Low

High

OFF 

ON

PV 

Low

High

OFF 

ON 

PV

Low 

High

OFF 

ON 

PV 

Low

High

(Alarm set value is greater than 0.) 

(Alarm set value is greater than 0.) 

ON 

OFF 

PV

Band alarm 

Process low alarm 

Process high alarm 

OFF 

OFF 

ON 

PV

Low 

High

Low 

High

OFF 

ON 

PV

Low 

High

ON 

 

 

 

 

  Change Settings 

Example:  Change the ALM1 type from “Deviation high alarm (0001)” to 
 

“Deviation low alarm (0101)” 

1. 

Press the SET key three times at SL1 until SL4 is displayed. 

2. 

Press the shift key to high-light the hundreds digit. 

3. 

Press the UP key to change the number to 1. 

 
 
 
 

4. 

Press  the  SET  key  to  store  the  new  set  value.  The  display  goes  to  the 
next parameter. 

 
7.7 PV bias (Pb) 

The  value  set  in  the  PV  bias  is  added  to  the  input  value  (actual  measured 
value) to correct the input  value. The PV bias is used to correct the individual 
variations  in  the  sensors  or  when  there  is  difference  between  the  measured 
values (PV) of other instruments. 
Setting range: 

TC/RTD inputs:   

1999 to +9999  C [ F] or 

 

199.9 to +999.9  C [ F] 

 

Voltage/Current inputs: 

199.9 to +200.0 % 

Factory set value: 

TC/RTD inputs: 

0  C [ F] or 0.0  C [ F] 

Voltage/Current inputs:  0.0 % 

 
 

Continued on the next page. 

 

 

 

 

Input type selection 

SV 

PV 

 

SV 

PV 

 

Press the shift key while pressing
the  SET  key  for  5  seconds  with
the unlocked. 

PV/SV display mode or Parameter setting mode 

Input type selection 

SET key 

(SL1) 

SET key 

SET key 

Alarm1 type   
selection 

SET key 

(SL4) 

Alarm2 type   
selection 

SET key 

(SL5) 

SET key 

SET key 

SET key 

PV bias 

SET key 

(Pb) 

ON/OFF action 
differential gap 

SET key 

(oH) 

Alarm 1 differential gap

SET key 

(AH1) 

Alarm 2 differential gap

SET key 

(AH2) 

Setting limiter high 

SET key 

(SLH) 

Setting limiter low 

SET key 

(SLL) 

Temperature unit and 
cooling type selection 

 

SV 

PV 

SV

PV

Содержание REX-C100

Страница 1: ...t responsible for any damage and or injury resulting from the use of instruments made by imitating this instrument Periodic maintenance is required for safe and proper operation of this instrument Some components have a limited service life or characteristics that change over time Every effort has been made to ensure accuracy of all information contained herein RKC makes no warranty expressed or i...

Страница 2: ...icinity of the instrument that could affect operation use a noise filter Shorten the distance between the twisted power supply wire pitches to achieve the most effective noise reduction Always install the noise filter on a grounded panel Minimize the wiring distance between the noise filter output and the instrument power supply terminals to achieve the most effective noise reduction Do not connec...

Страница 3: ...NC NO OUT 5 6 7 Ground 1 Terminals which are not used according to the controller type are all removed Use the solderless terminal appropriate to the screw size OUT T2 T1 G 5 7 6 Trigger for triac driving OUT 7 6 Voltage pulse Current Relay contact NO OUT2 NO OUT1 4 5 6 7 OUT2 OUT1 4 5 6 7 100 240V AC 24V DC 24V AC 3 3 2 2 3 2 L N L N Voltage pulse Current Input Current transformer input 20 19 CT ...

Страница 4: ...ter autotuning is completed AT lamp will go out Control output lamps OUT1 Yellow OUT2 Green OUT1 Lights when control output is turned on OUT2 Lights when cool side control output is turned on 6 DOWN key Decrease numerals 7 UP key Increase numerals To avoid damage to the instrument never use a sharp object to press keys SET This instrument returns to the PV SV display mode if no key operation is pe...

Страница 5: ... flow Heater break malfunction of the control device etc When the control output is ON and the current transformer input value is equal to or less than the heater break determination point for the preset number of consecutive sampling cycle an alarm is activated Over current or short circuit When the control output is OFF and the current transformer input value is equal to or greater than the heat...

Страница 6: ... key to change 1 to 0 SV PV 6 Press the SET key to store the new set value The display goes to the next parameter and the Initialization mode is unlocked SV PV 7 Press the shift key for 5 seconds while pressing the SET key to go to the Initialization mode When the controller goes to the Initialization mode SL1 will be displayed SV PV SV PV If the control is set to the initial set mode all outputs ...

Страница 7: ...ned to ALM2 When the Heater Break Alarm HBA is provided Factory set value varies depending on the instrument specification Set value Details of setting 0000 No alarm 0001 Deviation high alarm 0101 Deviation low alarm 0010 Deviation high low alarm 0110 Band alarm 0011 Process high alarm 0111 Process low alarm 1001 Deviation high alarm with hold action 1101 Deviation low alarm with hold action 1010 ...

Страница 8: ...n off the power at once If an error occurs after the power is turned on again please contact RKC sales office or the agent Over scale and Underscale Measured value PV Flashing PV is outside of input range Check Input type Input range and connecting state of sensor Confirm that the sensor or wire is not broken Flashing Over scale PV is above the high input display range limit Flashing Underscale PV...

Отзывы: