background image

5

 

Symbol 

Name 

Setting range 

Description 

Factory set value

 

Heater break 
alarm (HBA) set 
value 

1

 

0.0 to 100.0 A 

Alarm  value is set by referring to input  value 
from the current transformer (CT). 
Used only for single-phase. 

0.0 

 

Control  loop  break
alarm (LBA) time 

2

 

0.1 to 200.0 minutes 

Set control loop break alarm (LBA) set value. 

8.0 

 

LBA deadband 

3

 

TC/RTD inputs: 
  0 to 9999  C [ F] 
Voltage/Current inputs: 
  0 to 100 % of input span 

Set the area of not outputting LBA. 
No LBA deadband functions with 0 set. 
  Differential gap : 
  TC/RTD inputs:   

0.8  C [ F] 

Voltage/Current inputs: 0.8 % of input span 

 

 

Autotuning (AT) 
 

0: AT end or cancel 
1: AT start or execution 

Turns the autotuning ON/OFF. 

 

Proportional band 

TC/RTD inputs: 
  1 (0.1) to span 
  0.1  C [ F] resolution: 
  Within 999.9  C [ F] 
Voltage/Current inputs: 
  0.1 to 100.0 % of input span 
0 (0.0): ON/OFF action 

Set when PI, PD or PID control is performed. 
Heat/Cool PID action: Proportional band 
setting on the heat-side. 
 
  ON/OFF action differential gap: 
  TC/RTD inputs:   

2 (0.2)  C [ F] 

  Voltage/Current inputs:  0.2 % of input span 

TC/RTD inputs: 
  30 (30.0) 
 
Voltage/Current   
inputs: 3.0 

 

Integral time 

1 to 3600 seconds 

(0 second: PD action) 

Set the time of integral action to eliminate the 
offset occurring in proportional control. 

240 

 

Derivative time 

1 to 3600 seconds 

(0 second: PI action) 

Set the time of derivative action to improve 
control stability by preparing for output 
changes. 

60 

 

Anti-reset  windup 
(ARW) 

1 to 100 % of heat-side proportional 

band (0 %: Integral action OFF) 

Overshooting and undershooting are 
restricted by the integral effect. 

100 

 

Heat-side 
proportioning 
cycle 

1 to 100 seconds 
(Not displayed if the control output is 
current output.) 

Set control output cycle. 
Heat/Cool PID action: 
Heat-side proportioning cycle 

Relay contact output: 20

Voltage pulse output/ 
Trigger output for triac 
driving: 2 

 

Cool-side 
proportional band 

1 to 1000 % of heat-side 
proportional band 

Set cool-side proportional band when 
Heat/Cool PID action. 

100 

 

Deadband 

TC/RTD inputs: 
 

10 to +10  C [ F] or   

 

10.0 to +10.0  C [ F] 

Voltage/Current inputs: 
 

10.0 to +10.0 % of input span 

Set control action deadband between 
heat-side and cool-side proportional bands. 
Minus (

) setting results in overlap. 

0 or 0.0 

 

Cool-side 
proportioning 
cycle 

1 to 100 seconds 
(Not displayed if the control output is 
current output.) 

Set control cool-side output cycle for 
Heat/Cool PID action. 

Relay contact output: 20

Voltage pulse output: 2

 

 

Set data lock 
(LCK) 

0100:  No set data locked 
 

(All parameters changeable) 

0101:  Set data locked 
 

(All parameters locked) 

0110:  Only the set value (SV) is 
 

changeable with the set data 

 

locked 

Performs set data change enable/disable. 

0100 

 

1

 Heater Break Alarm (HBA) function 

The  HBA  function  monitors  the  current  flowing  through  the  load  by  a 
dedicated  current  transformer  (CT),  compares  the  measured  value  with 
the HBA set value, and detects a fault in the heating circuit. 

 

Low  or  No  current  flow  (Heater  break,  malfunction  of  the  control 
device, etc.): 
When the control output is ON and the current transformer input value is 
equal  to or  less  than  the  heater break determination point  for  the  preset 
number of consecutive sampling cycle, an alarm is activated. 
Over current or short-circuit: 
When the control output is OFF and the current transformer input value is 
equal  to  or  greater  than  the  heater  break  determination  point  for  the 
preset number of consecutive sampling cycle, an alarm is activated. 
 

Precaution for HBA setting: 

  Displayed only for when HBA is selected as Alarm 2. 
  HBA is not available on a current output. 
  Set the set value to approximately 85 % of the maximum reading of the 

CT input. 

  Set the set  value to a slightly smaller  value  to prevent a  false alarm if 

the power supply may become unstable. 

  When  more  than  one  heater  is  connected  in  parallel,  it  may  be 

necessary  to  increase  the  HBA  set  value  to  detect  a  single  heater 
failure. 

  When the current transformer is not connected or the HBA set value is 

set to “0.0,” the HBA is turned on. 

 

2

 Control Loop Break Alarm (LBA) function 

The LBA function is used to detect a load (heater) break or a failure in the 
external actuator (power controller, magnet relay, etc.), or a failure in the 
control  loop  caused  by  an  input  (sensor)  break.  The  LBA  function  is 
activated  when  control  output  reaches  0  %  or  100  %.  LBA  monitors 
variation  of  the  measured  value  (PV)  for  the  length  of  LBA  time.  When 
the  LBA  time  has  elapsed  and  the  PV  is  still  within  the  alarm 
determination range, the LBA will be ON. 

 

Precaution for LBA setting: 

  Displayed only for when LBA is selected as Alarm 1 or Alarm 2. 
  No LBA function can be used at Heat/Cool PID control action. 
  The LBA function can not be activated when AT function is turned on. 
  The  LBA  function  is  activated  when  control  output  reaches  0  %  or 

100  %.  The  time  required  for  the LBA  output  to  turn  on includes both 
the time from the initial occurrence of  loop failure and the LBA setting 
time. Recommended setting for LBA is for the set  value of the LBA to 
be twice the value of the integral time (I). 

  If LBA setting time does not match the controlled object requirements, 

the LBA selling time should be lengthened. 
If setting  time is  not correct,  the LBA  will  malfunction by  turning on or 
off at inappropriate times or not turning on at all. 

 

3

 LBA Deadband function 

The  LBA  may  malfunction  due  to  external  disturbances.  To  prevent 
malfunctioning due  to external  disturbance, LBA deadband  (LBD) sets a 
neutral  zone  in  which  LBA  is  not  activated.  When  the  measured  value 
(PV) is within the LBD area, LBA will not be activated.  If the LBD setting 
is not correct, the LBA will not work correctly. 

 
 
 
 
 
 
 
 
 

 

*  TC and RTD inputs: 0.8  C [ F] (fixed) 

 

Voltage/Current inputs: 0.8 % of input span (fixed) 

A:  During temperature rise: Alarm area 
 

During temperature fall:  Non-alarm area 

B: During temperature rise: Non-alarm area

B:  During temperature rise: Non-alarm area 
 

During temperature fall:  Alarm area 

LBD differential gap* 

Alarm area

Alarm area

Non-alarm area 

Set value (SV) 

LBD set value

Low 

High 

A

Содержание REX-C100

Страница 1: ...t responsible for any damage and or injury resulting from the use of instruments made by imitating this instrument Periodic maintenance is required for safe and proper operation of this instrument Some components have a limited service life or characteristics that change over time Every effort has been made to ensure accuracy of all information contained herein RKC makes no warranty expressed or i...

Страница 2: ...icinity of the instrument that could affect operation use a noise filter Shorten the distance between the twisted power supply wire pitches to achieve the most effective noise reduction Always install the noise filter on a grounded panel Minimize the wiring distance between the noise filter output and the instrument power supply terminals to achieve the most effective noise reduction Do not connec...

Страница 3: ...NC NO OUT 5 6 7 Ground 1 Terminals which are not used according to the controller type are all removed Use the solderless terminal appropriate to the screw size OUT T2 T1 G 5 7 6 Trigger for triac driving OUT 7 6 Voltage pulse Current Relay contact NO OUT2 NO OUT1 4 5 6 7 OUT2 OUT1 4 5 6 7 100 240V AC 24V DC 24V AC 3 3 2 2 3 2 L N L N Voltage pulse Current Input Current transformer input 20 19 CT ...

Страница 4: ...ter autotuning is completed AT lamp will go out Control output lamps OUT1 Yellow OUT2 Green OUT1 Lights when control output is turned on OUT2 Lights when cool side control output is turned on 6 DOWN key Decrease numerals 7 UP key Increase numerals To avoid damage to the instrument never use a sharp object to press keys SET This instrument returns to the PV SV display mode if no key operation is pe...

Страница 5: ... flow Heater break malfunction of the control device etc When the control output is ON and the current transformer input value is equal to or less than the heater break determination point for the preset number of consecutive sampling cycle an alarm is activated Over current or short circuit When the control output is OFF and the current transformer input value is equal to or greater than the heat...

Страница 6: ... key to change 1 to 0 SV PV 6 Press the SET key to store the new set value The display goes to the next parameter and the Initialization mode is unlocked SV PV 7 Press the shift key for 5 seconds while pressing the SET key to go to the Initialization mode When the controller goes to the Initialization mode SL1 will be displayed SV PV SV PV If the control is set to the initial set mode all outputs ...

Страница 7: ...ned to ALM2 When the Heater Break Alarm HBA is provided Factory set value varies depending on the instrument specification Set value Details of setting 0000 No alarm 0001 Deviation high alarm 0101 Deviation low alarm 0010 Deviation high low alarm 0110 Band alarm 0011 Process high alarm 0111 Process low alarm 1001 Deviation high alarm with hold action 1101 Deviation low alarm with hold action 1010 ...

Страница 8: ...n off the power at once If an error occurs after the power is turned on again please contact RKC sales office or the agent Over scale and Underscale Measured value PV Flashing PV is outside of input range Check Input type Input range and connecting state of sensor Confirm that the sensor or wire is not broken Flashing Over scale PV is above the high input display range limit Flashing Underscale PV...

Отзывы: