CONNECTION-WIRE DIAGRAM
See the right figure
TEST
• Slide the LUX switch to SUN position (below is SUN). Slide the
SENS switch to maximum (below is the maximum). Adjust the
TIME switch, slide 5” switch to ON position. (slide upwards)
• Switch on the power; the sensor and its connected lamp will have no
signal at the beginning. After Warm-up 30sec, the sensor can start
work .If the sensor receives the induction signal, the lamp will turn
on. While there is no another induction signal any more, the load
should stop working within 5sec and the lamp would turn off.
• Slide the LUX knob above on the minimum (moon). If the ambient light is more than 10LUX, the sensor would not
work and the lamp stop working too. If the ambient light is less than 3LUX (darkness), the sensor would work.
Under no induction signal condition, the sensor should stop working within 5sec..
Note: when testing in daylight, please turn LUX knob to (SUN) position, otherwise the sensor lamp
could not work! If the lamp is more than 60W, the distance between lamp and sensor should be 60cm at
least.
SOME PROBLEM AND SOLVED WAY
• The load does not work:
a. Please check if the connection of power source and load is correct.
b. Please check if the load is good.
c. Please check if the settings of working light correspond to ambient light.
• The sensitivity is poor:
a. Please check if there is any hindrance in front of the detector to affect it to receive the signals.
b. Please check if the ambient temperature is too high.
c. Please check if the induction signal source is in the detection field.
d. Please check if the installation height corresponds to the height required in the instruction.
e. Please check if the moving orientation is correct.
• The sensor can not shut off the load automatically:
a. Please check if there is continual signal in the detection field.
b. Please check if the time delay is set to the maximum position
c. Please check if the power corresponds to the instruction.