9 Technical specifications
Rittal air/water heat exchanger assembly instructions
29
EN
9
Technical specifications
Fig. 31:
Rating plate (technical data)
– Observe the mains connection data (voltage and
frequency) as per the rating plate.
– Observe the pre-fuse as per the specifications on
the rating plate.
Unit
Model No. SK
Basic controller,
RAL 7035
–
3209.100
3209.110
3209.140
3210.100
3210.110
3210.140
Comfort controller,
RAL 7035
–
3209.500
3209.510
3209.540
3210.500
3210.510
3210.540
Rated voltage
V
Hz
230, 1~,
50/60
115, 1~,
50/60
400, 2~,
50/60
230, 1~,
50/60
115, 1~,
50/60
400, 2~,
50/60
Rated current
A
0.40/0.48
0.85/0.95
0.25/0.30
0.44/0.50
0.90/1.0
0.25/0.30
Pre-fuse T
A
4.0/4.0
4.0/4.0
4.0/4.0
4.0/4.0
4.0/4.0
4.0/4.0
Motor circuit-breaker
–
–
–
–
–
–
–
Transformer circuit-breaker
–
–
–
–
–
–
–
Miniature circuit-breaker
–
Useful cooling output Q
k
L 35 W 10
to DIN 3168
W
l/h
2500
400
4000
400
Admissible pressure
bar
1 to 10
Water inlet temperature
°C
+1 to ±30
Temperature setting range
°C
+1 to +70
Noise level
dB (A)
58
58
58
58
58
58
Type of connection
–
Plug-in terminal strip
Protection category to EN 60 529
–
IP 55
Dimensions (W x H x D)
mm
597 x 417 x 475
Air throughput of the fans
(unimpeded air flow)
m
3
/h
1030
Weight
kg
23.5
27.5
27.5
25.5
29.5
29.5
.
Содержание SK 3209. Series