Rittal air/water heat exchanger assembly instructions
8 Storage and disposal
EN
8
Storage and disposal
During storage, the air/water heat exchanger must
stand upright.
Disposal can be performed at the Rittal plant.
Please contact us for advice.
Emptying:
During storage and transportation below freezing
point, the air/water heat exchanger should be
drained completely in the water supply direction us-
ing compressed air. This requires that the magnetic
valve be opened.
For the Basic controller: keep the rubberised poten-
tiometer display (5) pressed for ten seconds (for
access to the potentiometer, see also 6.1.3).
For the Comfort controller, this is achieved by simul-
taneously pressing the H2 (°C key) and H4 (/set key)
keys for five seconds. The magnetic valve is then
opened for approximately five minutes.
Note: Risk of damage!
The air/water heat exchanger must not
be subjected to temperatures above
+70°C during storage.