Commissioning 7
CMC-TC Wireless I/O-Unit
13
EN
7.5.3 Wireless System Range Estimate
Table 5 provides an indication of the expected ran-
ges for certain installation scenarios.
Scenario
Sensor range
Single enclosure
for steel door (closed)
up to 20m
for steel door (70% vented)
up to 35m
for glazed door
up to 45m
Single enclosure (side)
for steel door (closed)
up to 20m
for steel door (70% vented)
up to 25m
for glazed door
up to 25m
Note: These values are highly dependent on the
ambient reflection
Enclosure suite
for steel door (closed)
up to 6m
for steel door (70% vented)
up to 20m
for glazed door
up to 30m
Enclosure suite (side)
for steel door (closed)
up to 6m
for steel door (70% vented)
up to 10 m
for glazed door
up to 10 m
Note: These values are highly dependent on the
ambient reflection
Adjoining room (masonry: thickness 30 cm, concrete)
for steel door (closed)
up to 6m
for steel door (70% vented)
up to 8m
for glazed door
up to 10 m
Corridor (line of sight, LOS)
up to 50 m
Outdoor (line of sight, LOS)
up to 200m
Industrial building (line of sight, LOS)
up to 50 m
Tab. 5 Wireless ranges