Ritchie YELLOW JACKET R100 Скачать руководство пользователя страница 7

 

VAPOR & LIQUID (DIRECT) RECOVERY 

Vapor or Liquid Recovery is used to pull 
refrigerant directly out of the system to be 
serviced.  The refrigerant is then trans-
ferred to a recovery tank. 

Liquid Recovery is used when connecting 
to the high pressure side of the system to 
be serviced or any other service port that 
liquid refrigerant is present. 

Either Vapor or Liquid Recovery can be 
used when connecting to the low pres-
sure side or any other service port that 
vapor refrigerant is present. 

 

IMPORTANT:  If you are not sure 
whether liquid refrigerant is present, 
choose Direct Liquid Mode.  This mode 
limits the amount of liquid refrigerant 
entering the compressor.  Recovery of 
liquid refrigerant in the Vapor Recov-
ery mode can damage the compressor. 

If large quantities of liquid refrigerant are 
expected, use the liquid push-pull 
method.  Push-pull will transfer liquid 
refrigerant faster than direct liquid recov-
ery. 

The hose connections for vapor & liquid 
recovery are shown in the figure 2.  To 
perform vapor or liquid recovery, please 
follow the steps below: 

1. Turn off power to the system to be 

serviced. 

2. Turn the Suction Valve to “OFF” and 

the Discharge Valve to “RECOVER.” 

3. Connect the recovery unit, the system 

to be serviced, and the recovery tank 
as shown in the figure 2.  The suction 
hose can be connected to the liquid 
and/or vapor service ports.  

If you 

connect to the liquid service port, 
ensure you use Liquid Recovery. 

 

Also ensure the hose to the tank is 
connected to the DISCHARGE  port of 

the recovery unit. 

4. Open the vapor valve on the recovery 

cylinder. 

5. Turn the discharge valve (right) to 

“RECOVER” position. 

6. Turn the 

System Switch

 ”ON”.  The 

Green LED should energize. 

7. Turn the suction valve (left) to: 

“VAPOR RECOVERY” for vapor recovery 

from the vapor service 
port. 

“LIQUID RECOVERY” for liquid recovery 

from the liquid service 
port. 

CAUTION:  If unsure of the refriger-

ant’s phase, always choose 
the “LIQUID RECOVERY” 
position. 

Note:  If the Yellow LED energizes, the 
recovery tank is full.  Turn off power.  
Turn off both valves.  Exchange recovery 
tank with an empty one.  Repeat Steps 3-
6. 

If the Red LED energizes, the recovery 
unit is sensing a high-pressure limit.  Turn 
off power and check for restrictions.  If 
tank pressure is above 400 psig, ex-
change tank.  Repeat Steps 3-6. 

7. After the Suction Pressure Gauge indi-

cates the required vacuum, turn the 
discharge valve to “PURGE” to remove 
the remaining refrigerant from the re-
covery unit. 

8. When the Suction Pressure Gauge 

indicates a vacuum, Turn the SUC-
TION VALVE to “OFF”, Turn off the 
power to the recovery unit, and Discon-
nect the two refrigerant hoses. 

Recovery and Purge Operations are now 
complete.  The R100 is ready for the 
next job. 

Содержание YELLOW JACKET R100

Страница 1: ...1 R100 Oil Less Refrigerant Recovery Unit Operation Manual...

Страница 2: ...epth 13 25 in Weight 48 lb Welcome to simple efficient refrigerant recovery with your new YELLOW JACKET Refrigerant Recovery Unit R100 This unit combines the latest oil less compressor technology with...

Страница 3: ...isconnect Unit from Power Supply Before Servicing An electrical shock hazard is present when the unit is disas sembled Repair Damaged Parts Do not operate the unit with a defective part Repair unit to...

Страница 4: ...r 40 CFR part 82 subpart F or current equivalent Before operating this unit please read this manual thoroughly You must understand the procedures outlined in this manual Failure to follow these proced...

Страница 5: ...system does not allow for a solid column of liquid refrigerant to be formed When using push pull recovery the R100 will not recover to the required vacuum level in the recovered system Use a sight gla...

Страница 6: ...igh pressure limit Turn off power and check for restrictions If tank pressure is above 400 psig exchange tank Repeat Steps 3 6 7 Turn the Tank Vapor Valve to OFF Wait until suction pressure gauge indi...

Страница 7: ...ry tank as shown in the figure 2 The suction hose can be connected to the liquid and or vapor service ports If you connect to the liquid service port ensure you use Liquid Recovery Also ensure the hos...

Страница 8: ...charge Gauge Indicates the discharge pressure of the recovery unit s condenser 6 Cooling Fan This fan provides airflow through the condenser and across the compressor 7 Suction Valve Valve for selecti...

Страница 9: ...g the high pressure switch High differential pressure across compressor suction and discharge valves System to be serviced does not allow liquid recovery Plug in to energized socket Check socket for p...

Страница 10: ...10 Notes recovery tank hvac unit or appliance recovery tank REPAIR PARTS DIAGRAM...

Страница 11: ...rd 3 Compressor hoses 4 95154 Compressor includes head 5 95251 Suction Valve w Strainer 6 95190 Capacitor 7 95233 Compressor Relay 8 95252 Foam for Handles 9 95213 Low Pressure Gauge 10 95212 High Pre...

Страница 12: ...S A 04 06 FK 150834 Recovery Division 6701 West 110th Street Bloomington MN 55438 USA Phone 952 943 1333 Phone 800 769 8370 Fax 952 943 1605 Fax 800 322 8684 Email custserv yellowjacket com Web www y...

Отзывы: