Mounting of the Meter is featured with easy “Clip-
in” mounting. Push the meter in panel slot (size 92
x92 mm), it will click fit into panel with the four
integral retention clips on two sides of meter. If
required, additional support is provided with swivel
screws as shown in figure.
The front of the enclosure conforms to IP54.
Additional protection to the panel may be obtained
by the use of an Optional panel gasket. The
terminals at the rear of the product should be
protected from liquids.
The Meter should be mounted in a reasonably
stable ambient temperature and where the
operating temperature is within the range -20 to
0
70 C. Vibration should be kept to a minimum and
the product should not be mounted where it will be
subjected to excessive direct sunlight.
7. Installation
1 - 3mm for self clicking,
1 - 6mm for swivel screws
Panel Thickness :
1. In the interest of safety and functionality this product must be installed by a qualified engineer, abiding by any local regulations.
2. Voltages dangerous to human life are present at some of the terminal connections of this unit. Ensure that all supplies are de-
energised before attempting any connection or disconnection.
3. These products do not have internal fuses therefore external fuses must be used to ensure safety under fault conditions.
Caution
7.1 EMC Installation Requirements
This product has been designed to meet the certification of the EU directives when installed to a good code of
practice for EMC in industrial environments, e.g.
1. Screened output and low signal input leads or have provision for fitting RF suppression components,such as
ferrite absorbers, line filters etc., in the event that RF fields cause problems.
Note
:
It is good practice to install sensitive electronic instruments that are performing critical functions, in EMC
enclosures that protect against electrical interference which could cause a disturbance in function.
2. Avoid routing leads alongside cables and products that are, or could be, a source of interference.
3. To protect the product against permanent damage, surge transients must be limited to 2kV pk. It is good
EMC practice to suppress differential surges to 2kV at the source. Theunit has been designed to automatically
recover in the event of a high level of transients. In extreme circumstances it may be necessary to temporarily
disconnect the auxiliary supply for a period of greater than 5 seconds to restore correct operation.