if CtL as "u" the value entered in C01 will be the Capacitor Bank value. The value
entered in CXX will be the value for respective Capacitor Bank.
After setting the values for number of selected banks pressing the will move
forward to manual relay on-off function.
if CtL as bank mode ( 1 - 9 ), the value enetered in C01 will be set as the
multiplicand for Capacitor Banks.
Example:
The value set in Control Series is 3 - {1,2,3,3,3,3,3,3} and C01 is
2 kVAR then the Bank values will become C01(Bank1) = 2kVAr x 1 = 2 kVAr,
C02(Bank2) = 2kVAr x 2 = 4 kVAr, C03(Bank3) = 2kVAr x 3 = 6 kVAr and
so on.
3.9 Manual relay On - Off
The screen display "rLY".
pressing key shows relay number
corrosponding to capacitor. press
key shows relay current state. pressing
key on state screen enables relay
to switched ON or OFF depending on
current state relay state.
scroll to next capacitor
using key.
Sideby screens shown are possible
in relay test mode