6.1 User Assignable Modbus Registers:
This
contains the 20 user assignable registers in the address range of 0x200
instrument
(30513) to 0x226 (30551) (
see Table 8
).
Any of the parameter addresses ( 3X register addresses Table 4)) accessible in the
instrument can be mapped to these 20 user assignable registers.
Parameters (3X registers addresses ) that resides in different locations may be accessed
by the single request by re-mapping them to adjacent address in the user assignable
registers area.
The actual address of the parameters ( 3X registers addresses) which are to be assessed
via address 0x200 to 0x226 are specied in 4x Register 0x200 to 0x213 (
see Table 9).
30513
257
00
Modbus Start Address (Hex)
Assignable Reg 1
30515
258
02
02
Assignable Reg 2
30517
259
04
02
Assignable Reg 3
30519
260
06
02
Assignable Reg 4
30521
261
08
02
Assignable Reg 5
30523
262
0A
02
Assignable Reg 6
Table 8 : User Assignable 3X Data Registers
Address
(Register)
Parameter
Number.
Assignable Register
02
High Byte
Low Byte
Table 7 : Pulse1 & Pulse2 Conguration
4
Export Reactive Energy
Apparent Energy
Import Reactive Energy
Code
1
0
2
3
Conguration
Import Active Energy
Export Active Energy