Address
Parameter
Description
40019
Rs485 Set-up
Code
This address is used to set the baud rate, Parity, Number of
stop bits. Refer to Table 6 for details.
40021
Node
Address
This register address is used to set Device address
between 1 to 247 .
40023
Pulse Divisor
40025
Min - Reset
This address is used to reset the Min parameters value.
Write Zero value to this register to reset the Min parameters.
Writing any other value will return an error.
40027
Max - Reset
This address is used to reset the Max parameters value.
Write Zero value to this register to reset the Max parameters.
Writing any other value will return an error.
This address is used to set
pulse divisor
of the Pulse output.
Write one of the following values to this address
for Wh
:
1 : Divisor 1
10 : Divisor 10
100 : Divisor 100
1000
:
Divisor 1000 & in KWh & MWh Divisior will be
1 default.
Writing any other value will return an error.
Pulse rate divisor is set to 1, when Energy on Rs485 is set
to kWh or MWh.
40029
Analog Out 1-
Para Set
This address is used to set the parameter for Analog Output 1.
Write one of the parameter no. As per the options given in
Table 2 for Analog Output Parameters.
Writing any other value will return an error.
40031
Analog Out 2-
Para Set
This address is used to set the parameter for Analog Output 2..
Write one of the parameter no. As per the options given in
Table 2 for Analog Output Parameters.
Writing any other value will return an error.
54