![Rish Master 3430 Скачать руководство пользователя страница 49](http://html1.mh-extra.com/html/rish/master-3430/master-3430_operating-manual_1464342049.webp)
Query :
Start Address High : Most signicant 8 bits of starting address of the parameter requested.
Start Address low :Least signicant 8 bits of starting address of the parameter requested.
Number of register Hi : Most signicant 8 bits of Number of registers requested.
Number of register Lo : Least signicant 8 bits of Number of registers requested.
(Note : Two consecutive 16 bit register represent one parameter.)
Device Address
Function Code
Start Address High
Start Address Low
Number of Registers Hi
Number of Registers Lo
CRC Low
CRC High
01 (Hex)
03 (Hex)
00 (Hex)
0A (Hex)
00 (Hex)
02 (Hex)
E4 (Hex)
09 (Hex)
Each setting is held in the 4X registers .ModBus code 03 is used to read the current setting
and code 16 is used to write/change the setting. Refer
Table 5
for 4 X Register addresses.
Example : Reading System type
System type : Start address = 0A (Hex) Number of registers = 02
Note :Number of registers = Number of Parameters x 2
Accessing 4 X register for Reading & Writing :