9
Visual / Audible Indicators
If the red LED indicator (
see Figure 10
) flashes once every 30 seconds, the detector
is functioning normally.
If the red LED indicator flashes constantly and repetitive beeps are heard, the
detector is reacting to a fire alarm (primary or secondary).
A short beep once every 30 seconds indicates low battery or trouble condition.
If a fire alarm is activated, press the cover up firmly (
see Testing the detector
) to
silence the alarm and temporarily disable (for approx. 10 minutes) the alarm
activation.
Detector parameters
The following detector parameters can be defined from the system receiver:
Parameter
Option
Operational Mode:
Smoke only*, Heat only or Smoke and Heat
Supervision Time:
1-255 (15 min*)
* = default
See your system receiver’s installation / configuration manual for more
information about defining detector parameters.
Testing the detector
To ensure that your detector is functioning correctly, test it once a week using the
following procedure:
1.
Press the cover up firmly (
see Figure 12
). If the detector is functioning
correctly, a fire alarm is activated (
see Visual / Audible Indicators
) and an alert
message is sent to the system receiver.
NOTE:
A short beep once every 30 seconds
indicates that the test is unsuccessful.
You must have the detector repaired or
replaced immediately.
Figure 12
2.
Release pressure to restore the alarm activation.