background image

AI-Fire Smoke Sensing 

Network Camera

Quick Start Guide

General

This manual introduces the functions and operations of the 5 MP IR AI-fire Smoke Sensing Network 

Camera (hereinafter referred to as "the Device").

Models

DHI-HY-SAV849HAP-E, DHI-HY-SAV849HAN-E

Safety Instructions

The following categorized signal words with defined meaning might appear in the manual.

Foreword

Signal Words

Meaning

 DANGER

Indicates a high potential hazard which, if not avoided, will result in death 

or serious injury. 

 WARNING

Indicates a medium or low potential hazard which, if not avoided, could 

result in slight or moderate injury.

 CAUTION

Indicates a potential risk which, if not avoided, could result in property 

damage, data loss, lower performance, or unpredictable result.

 TIPS

Provides methods to help you solve a problem or save you time.

 NOTE

Provides additional information as the emphasis and supplement to the 

text.

About the Manual

● 

 The manual is for reference only. If there is inconsistency between the manual and the actual 

product, the actual product shall prevail.

● 

 We are not liable for any loss caused by the operations that do not comply with the manual.

● 

 The manual would be updated according to the latest laws and regulations of related jurisdictions. 

For detailed information, refer to the paper manual, CD-ROM, QR code or our official website. If 

there is inconsistency between paper manual and the electronic version, the electronic version 

shall prevail.

● 

 All the designs and software are subject to change without prior written notice. The product 

updates might cause some differences between the actual product and the manual. Please 

contact the customer service for the latest program and supplementary documentation.

● 

 There still might be deviation in technical data, functions and operations description, or errors in 

print. If there is any doubt or dispute, we reserve the right of final explanation.

● 

 Upgrade the reader software or try other mainstream reader software if the manual (in PDF 

format) cannot be opened.

● 

 All trademarks, registered trademarks and the company names in the manual are the properties of 

their respective owners.

● 

 Please visit our website, contact the supplier or customer service if there is any problem occurring 

when using the device.

● 

 If there is any uncertainty or controversy, we reserve the right of final explanation.

The manual will help you to use the Device properly. Read the manual carefully before using the 

Device, and keep it well for future reference.

Operation Requirements

WARNING

Never ignore any alarm. Failure to respond may lead to serious injury or death.

● 

 Make sure that the power supply of the device works properly before use.

● 

Use the device according to the operating environment.

● 

Only use the device within the rated power range.

● 

 Transport, use and store the device under allowed humidity and temperature conditions.

● 

 Prevent liquids from splashing or dripping on the device. Make sure that there are no objects filled 

with liquid on top of the device to avoid liquids flowing into it.

Installation Requirements

WARNING

● 

 Strictly abide by local electrical safety standards, and make sure that the voltage in the area is 

steady and conforms to the power requirements of the device.

● 

 Failure to properly install and operate this device will prevent proper operation of the Device and 

will prevent its response to fire hazards.

● 

 All installation and operations shall conform to your local electrical safety regulations, fire 

protection regulations, and other relevant regulations.

● 

 Make sure that the application scenario conforms to installation requirements. Contact your local 

retailer or customer service center if there is any problem.

● 

 Use the Device according to the operating environment.

● 

 Keep the original packing material well because you might need it to pack the Device and

● 

send it back for repair.

● 

 Observe all safety procedures and wear required protective equipment provided for your use while 

working at heights.

● 

Do not expose the device to direct sunlight or heat sources.

● 

 Keep the original packing material well because you might need it to pack the device and send it 

back for repair.

● 

 Make sure the application scenario conforms to installation requirements. Contact your local 

retailer or customer service center if there is any problem.

● 

 All installation and operations shall conform to your local electrical safety requirements, fire 

protection regulations, and other relevant regulations.

Maintenance Requirements

● 

Do not clean the device with any cleaning products.

● 

 Do not paint the device. Paint will seal the bents and interfere with the sensor’s ability to work 

normally.

Important Safeguards and Warnings

1.1 Introduction

Together with high-performance microprocessor and advanced electronic technology, the 5 MP IR

AI-fire Smoke Sensing Network Camera has the characteristics of high sensitivity and stability. 

Based on the mounting bracket, it can be easily installed on the ceiling. With built-in high-decibel 

buzzer, it will send out a sound and light alarm signal in time to remind users to take effective 

measures immediately when the smoke concentration reaches the alarm setting value. Application 

scenarios include chain stores, unattended base stations, unmanned power distribution rooms, ATM 

areas, libraries and places where both fire alarm and video surveillance are needed.

1.2 Dimensions

Figure 1-1 Dimensions (mm[inch])

1.3 Technical Information

Table 1-1 Specification

Specification

Introduction

Model

DHI-HY-SAV849HAP-E, DHI-HY-SAV849HAN-E

Communication

1 RJ-45 PoE 10M/100M Ethernet ports

Indicators

● 

 Standby: Green indicator flashes once per minute

● 

Alarm: Red indicator flashes once per second

● 

Fault: Red indicator flashes once per minute

● 

 Self-test: Red indicator flashes once per second

● 

 Low voltage: Red indicator flashes once per minute

Protection Area of Smoke Sensor 30 m²–60 m²
Operating Principle

Photoelectric

Alarm Method

Sound and LED Indicator

Power Supply

DC12V / PoE and 3V lithium battery

Operating Current

≤30uA (Camera excluded)

≤300mA (Camera included)

Back-up Battery Life

3–5 years

Operating Temperature

–10°C to +55°C (+14°F to +131°F)

Operating Humidity

0%–95% RH (non-condensing) 

1.4 Cable

 

 

● 

Cable type might vary with different devices, and the actual product shall prevail.

● 

 Please waterproof all the cable joints with insulating tape and waterproof tape to avoid short circuit 

and water damage. For the detailed operation, see the FAQ manual.

Figure 1-2 Cable list

Table 1-2 Cable information

No.

Port name

Description

1

Audio input

RCA port. Connects to sound pickups to receive audio signal.

2

Audio output

RCA port. Connects to speaker to output audio signal.

3

Ethernet port

● 

Connects to network with network cable.

● 

Provides power to the device with PoE.

PoE is available on select models.

4

Alarm I/O

Includes alarm signal input and output ports, and the number of I/O 

ports might vary on different devices

5

Power input

Inputs 12 VDC power. Be sure to supply power as instructed in the 

manual.

Device damage might occur if power is not supplied correctly.

6

RS 485 port

Controls external devices.

For more information about I/O port, see Table 1-3. 

Port

Port Name

Description

Alarm I/O

ALARM_OUT1

Outputs alarm signal to alarm device.

When connecting to alarm device, only the ALARM_

OUT port and ALARM_OUT_GND port with the same 

number can be used together.

ALARM_OUT_GND1
ALARM_OUT2

ALARM_OUT_GND2

ALARM_IN1

Receives the switch signal of external alarm source.

Connect different alarm input devices to the same 

ALARM_IN_GND port.

ALARM_IN2

ALM_IN_GND

Table 1-3 Alarm information

1.5 Alarm Configuration

The Device can connect to external alarm input/output device through input/output port.

Cut off power before connecting cables.

Step 1 

  Connect alarm input device to alarm input port of I/O cable.

Device collects different states of alarm input port when the input signal is idling and being 

grounded.

● 

 When input signal is connecting to +3V to +5V or idling, the Device collects logic "1".

● 

When input signal is grounded, the Device collects logic "0."

Figure 1-3 Alarm input

Step 2 

   Connect alarm output device to the alarm output end of the I/O port. The alarm output is 

open-drain output, which works in the following modes.

● 

 Mode A: Level application. Alarm outputs high and low level, and the alarm outlet is OD, 

which requires external pull-up resistance (10K Ohm typical) to work. The maximum 

external pull-up level is 12V, maximum port current is 300mA and the default output signal 

is high level (external pull-up voltage). The default output signal switches to low level 

when there is alarm output (As long as the operating current below 300mA, the output low 

level voltage is lower than 0.8V).

● 

 Mode B: Switch application. Alarm output is used to drive external circuit, the maximum 

voltage is 12V and the maximum current is 300mA. If the voltage is higher than 12V, 

please use an additional electric relay.

Figure 1-4 Alarm output

V1.0.0

Product Information

1

Step 3 

  Log in web interface, and configure alarm input and alarm output in alarm setting.

● 

 The alarm input in the web interface is corresponding to the alarm input end of the I/O 

port. There will be high level and low level alarm signal generated by the alarm input 

device when alarm occurs, set the input mode to "NO" (default) if the alarm input signal is 

logic "0" and to "NC" if the alarm input signal is logic "1".

● 

 The alarm output in the web interface is corresponding to the alarm output end of the 

device, which is also alarm output end of the I/O port.

Alarm Classification

Smoke alarm,  fault alarm, undervoltage alarm, AI alarm

Alarm Sound Pressure

≥80 dB (A) @ 3 m (9.84 ft)

Image Sensor

1/2.7" CMOS

Focal Length

2.0mm

Max. Pixel

500W

Day/Night

Auto (ICR)

Video Compression

H.265;H.264;H.264H;H.264B

L:W

16:9

Max. Frame Rate

2592(H)×1944(V)

Bit Rate Control

Variable/Constant

Alarm Linkage

Smoke alarm, AI alarm

Reset

Support

Alarm Input

2 channels in: 5mA 3V–5V DC

Alarm Output

2 channels out: 300mA 12V DC

Temperature Measuring Range

–20°C to +120°C (-4°F to +248°F)

Dimensions

φ120 mm × H79mm (4.72" × 3.11" )

Weight (with battery)

420 g (0.93 lb)

Figure 1-5 The alarm interface

Device initialization and IP address setting can be finished with the "ConfigTool" or in web interface. 

For more information, see the Web Operation Manual.

● 

 Device initialization is available on select models, and it is required at first use or after the device 

being reset.

● 

 Device initialization is available only when the IP addresses of the device (192.168.1.108 by 

default) and the PC stay in the same network segment.

● 

 Plan useable network segment properly to connect the device to the network.

● 

 The following figures and interfaces are for reference only, and the actual product shall prevail.

2.1 Initializing Device

Step 1 

 Double-click "ConfigTool.exe" to open the tool.

Step 2 

 Click 

 .

The 

Modify IP

 interface is displayed. See Figure 2-1.

Network Configuration

2

1.2.51.32.19297-000

Содержание DHI-HY-SAV849HAP-E

Страница 1: ...AI Fire Smoke Sensing Network Camera Quick Start Guide V1 0 0 1 2 51 32 19297 000...

Страница 2: ...e operations that do not comply with the manual The manual would be updated according to the latest laws and regulations of related jurisdictions For detailed information refer to the paper manual CD...

Страница 3: ...ion scenario conforms to installation requirements Contact your local retailer or customer service center if there is any problem All installation and operations shall conform to your local electrical...

Страница 4: ...85 port Controls external devices For more information about I O port see Table 1 3 Port Port Name Description Alarm I O ALARM_OUT1 Outputs alarm signal to alarm device When connecting to alarm device...

Страница 5: ...A If the voltage is higher than 12V please use an additional electric relay Figure 1 4 Alarm output Step 3 Log in web interface and configure alarm input and alarm output in alarm setting The alarm in...

Страница 6: ...rns to Initialized 2 2 Modifying Device IP Address You can modify IP address of one or multiple devices in one time This section is based on modifying IP addresses in batch Modifying IP addresses in b...

Страница 7: ...gth of the device must be above the medium Avoid the installation in following areas High humidity areas such as kitchens water heaters and bathrooms Areas that are dusty dirty or insects frequent Are...

Страница 8: ...ith self tapping screws Step 4 Install the battery 1 Correctly insert the battery lead terminals 2 Place the battery in the battery compartment and arrange the wiring harness Step 5 Rotate to install...

Страница 9: ...ry minute Please replace the battery in time 5 1 Green Power indicator light does not flash Solutions Check the connection of power cable Contact with manufacturer 5 2 Press Test button there is no al...

Отзывы: