M-UM038-01 RP 460 Reference and Test
DMT
Example 4: Multimode Fiber, Point-to-Point, 1 Jumper
Fiber Type
Multimode
Connectors Used
LC
Test Jumper Setup
Single
OPM Used
RP 460
OLS Used
DLS 350
Fiber-Under-Test
The fiber-under-test is multimode with LC
connectors on each end. In this example, the
fiber-under-test is 400 meters long.
Test Jumper
The test jumper is a one-meter multimode fiber
with SC and LC connectors. The SC connector will
be plugged into the DLS 350 LED source and the
LC connector will be used to interface with the
fiber-under-test.
Power Meter
The RP 460 power meter is set to
the 850nm wavelength. The 1300nm
wavelength may also be used. Always
match the wavelength on the RP 460
to the wavelength on the DLS 350. The
adapter on the RP 460 is the AC 029 LC
adapter.
Light Source
The DLS 350 LED source is set to the
850nm wavelength. The 1300nm
wavelength may also be used. The
adapter is the default AC 022B SC adapter.
400m Fiber
1m Jumper